Parameter
Number
Initialization / Adjustment Function (continued)
b84
Reset Functions
Resets the factory defaults or clears the fault history.
Settings: 00=Clear fault history
01=Reset defaults
Note: To activate this parameter, set the value and
press Enter, then hold the PROGram, Up Arrow, Down
Arrow, and Stop for 3 seconds, release only Stop until
the display is blinking, then release all of the keys.
Note: Defaults will reset to factory settings determined
by b85 [
FACTORY DEFAULTS SELECT
b85
Factory Defaults Select
Selects which set of defaults to use.
Settings: 06=Previous K version (50 Hz, Europe only)
07=U version (60 Hz)
Note: Settings 00 – 05 are not used.
*b86
Process Display Scale Factor
Sets the frequency factor for d07 [
Also sets the multiplier that is applied to the output
frequency for the FM pulse signal.
This parameter can be changed while motor is running
b87
STOP Key Select
This parameter is not active when b85 [
DEFAULTS SELECT
!
b88
FRS Select
Selects the operation of the drive after a digital input
(C01 – C05) setting 11{FRS} input is removed.
Settings: 00=0 Hz start
01=Synchronization of motor speed after
waiting period programmed via b03 [
TIME
b89
Keypad Display
Selects the display parameter that will be shown on the
fixed keypad when the remote keypad is connected.
Settings: 01 = d01 [
02 = d02 [
03 = d03 [
04 = d04 [
05 = d05 [
06 = d06 [
07 = d07 [
b92
(Reserved)
Reserved for future use. DO NOT CHANGE
3-18
Parameter Name/Description
]
PROCESS DISPLAY
] is set to 06 or 07.
ATTENTION: If parameter b85 settings
00 through 05 are activated, this
parameter will control the operation of
the keypad STOP key. Setting 00 will
enable the STOP key and 01 will disable
the STOP key. Disabling the STOP key
is not recommended as it could result in
personal injury, loss of life, or equipment
damage.
].
OUTPUT FREQUENCY
OUTPUT CURRENT
DIRECTION OF ROTATION
PID PROCESS DISPLAY
DIGITAL INPUT STATUS
]
OUTPUT STATUS
PROCESS DISPLAY
Min./Max
00 to 01
01 to 07
0.1 to 99.9
].
00/01
FACTORY
00 to 01
RESTART
01 to 07
]
]
]
]
]
]
00/01
Range
Units
Numeric
Value
Numeric
Value
N/A
Numeric
Value
Numeric
Value
Numeric
Value
00
SP120 AC Drive Installation and Operation
Factory
Default
01
07
30.0
00
00
01