Parameter
Number
Preset Frequencies (continued)
*A21
Preset Frequency 1
*A22
Preset Frequency 2
*A23
Preset Frequency 3
*A24
Preset Frequency 4
*A25
Preset Frequency 5
*A26
Preset Frequency 6
*A27
Preset Frequency 7
*A28
Preset Frequency 8
*A29
Preset Frequency 9
*A30
Preset Frequency 10
*A31
Preset Frequency 11
*A32
Preset Frequency 12
*A33
Preset Frequency 13
*A34
Preset Frequency 14
*A35
Preset Frequency 15
*A38
Jog Frequency
This parameter sets the frequency the drive will output
when it receives a valid jog command.
This parameter can be changed while motor is running.
A39
Jog Stop Mode
This parameter sets the stop method when the jog input
is removed.
Settings: 00=Coast
01=Ramp
02=DC Brake (See A53 [
Parameters and Programming
Parameter Name/ Description
The programmed value sets
the frequency that the drive
outputs when selected. (Refer
to digital input settings table in
Chapter.2).
Note: If a preset frequency
input is active, the keypad
frequency pot and analog
frequency commands will be
ignored.
Note: The value of any Preset
Frequency can be changed via
F01 [
FREQUENCY COMMAND
when the Preset Frequency is
activated via the digital inputs.
These parameters can be
changed while motor is
running.
DC WAIT TIME
A55 [
])
DC HOLD TIME
Min./Max
Range
0.0 to 360.0 0.1 Hz
0.0 to 360.0 0.1 Hz
0.0 to 360.0 0.1 Hz
0.0 to 360.0 0.1 Hz
0.0 to 360.0 0.1 Hz
0.0 to 360.0 0.1 Hz
0.0 to 360.0 0.1 Hz
0.0 to 360.0 0.1 Hz
0.0 to 360.0 0.1 Hz
0.0 to 360.0 0.1 Hz
]
0.0 to 360.0 0.1 Hz
0.0 to 360.0 0.1 Hz
0.0 to 360.0 0.1 Hz
0.0 to 360.0 0.1 Hz
0.0 to 360.0 0.1 Hz
0.5 to 9.9
00 to 02
] –
English
Factory
Units
Default
0.0
3.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
0.0
0.1Hz
5.0
Numeric
01
Value
3-11