16
{AT}
4-20mA Select
18
{RS}
Reset
19
{PTC}
PTC Input
20
{STA}
3-wire run
21
{STP}
3-wire stop
22
{F/R}
3-wire
Forward/Reverse
2-14
Table 2.5 – Programmable Digital Input Functions
Function
Activates input terminal OI for use as a 4-20 mA input. If no input
terminal is programmed for this setting, the factory default input is O
(0-10V) and the output frequency will correspond to the value of the
inputs to the O and/or OI control inputs.
Note: Parameter A01 [
what source the output frequency is commanded.
Used to clear a fault condition. If a 18 {RS} command is given during
operation, the output IGBTs are switched off and the motor will coast.
18 {RS} (NO)
Fault indication
This input can only be programmed to digital input terminal 5 and
the PTC should be referenced to terminal L.
If the PTC resistance exceeds 3k Ohms, the output voltage to the motor
will be switched off and an E35 fault code will be issued.
5
L
3-wire (Momentary) control inputs. Both settings 20 {STA} and 21 {STP}
must be programmed as digital inputs for 3-wire control to function. If 20
{STA} is programmed into any digital input then 2-wire (maintained)
control will not function.
Note: 3-wire stop command (21 {STP}) cannot be used to clear a fault.
20{STA} (NO)
21{STP} (NC)
22 {F/R (NO)
Motor Speed
Description
FREQUENCY COMMAND SELECT
SP120 AC Drive Installation and Operation
] determines from