1.7 CONFIGURATION OF THE DHW PRIORITY SCHEDULE
To access the configuration parameters, insert password "48".
Menu
Par
Label
Description
label
Start DHW priority period:
124
OmP
ning
SAm1
End DHW priority period:
125
OFFP
ning
If these parameters are not configured, domestic hot water production will always have priority over air conditioning.
1.8 CONFIGURATION OF THE ANTI-LEGIONELLA FUNCTION
To access the configuration parameters, insert password "48".
Menu
Par
Label
Description
label
DHW heat treatment start frequency (anti-legionella)
133 CYCA
carried out at. At 0, the function is disabled
134
SEtA
DHW heat treatment set point (anti-legionella)
SAni
DHW heat treatment start period (anti-legionella) The minimum
continuous amount of time that the water temperature in the storage
135
tiMA
tank stays above the set point value
136 HOUA DHW heat treatment start time (anti-legionella)
In detail:
CYCA: Number of consecutive days, without any anti-legionella treatment, after which point a forced treatment is run.
SEtA: Temperature in the storage tank, above which the anti-legionella treatment is considered as having been carried out (par.112 > par.134).
tiMA: Minimum continuous time, that the above condition lasts for (par.112 > par.134), after which point the anti-legionella treatment is conside-
red as having been carried out.
HOUA: Time of day that the forced treatment is carried out.
Forced treatment means switching on the electric resistor, so that par.112 > par.134, for an amount of time equal to par.135.
Obviously, if during normal operation both conditions required for the anti-legionella treatment are fulfilled, the number of days counted without any
treatment starts from zero again.
The time of day that DHW production has priority over air conditio-
The time of day until DHW production has priority over air conditio-
The time interval, in days, that the anti-legionella treatment will be
Enclosed documents
124
U.m.
Range
max Default t
min
h:
00:00 23:59
00:00
min
h:
00:00 23:59
23:59
min
U.m.
Range
max Default t
min
day
0
30
0
°C
50
70
60
min
1
30
15
h:
00:00 23:59
02:00
min
Correct
Address
16397
16398
Correct
Address
16405
16406
16407
16408