Description
Relevant part Verification method
Code
Flow tempera-
DRAIN TEMP.
A8
ture sensor
SENSOR
error
PCB MAIN
C0
PCB MAIN
error
FUSE CF7
Upper fan
C1
motor error
FAN MOTOR
PCB MAIN
Outdoor
OUTDOOR
C2
temperature
TEMP.
sensor error
SENSOR
Fuse CF7,
CF6
Lower fan
C3
motor error
FAN MOTOR
PCB MAIN
Increase in
Incorrect
temperature
installation
C4
(over 110°C)
of the PCB
DRAIN TEMP.
MAIN
PCB MAIN
PCB MAIN
DRAIN TEMP.
C5
sensor error
PCB MAIN
PCB MAIN
C6
PCB MAIN
error
Incorrect PCB
MAIN - PCB
TERMINAL
BLOCK con-
nection
Serial error
C7
PCB
Earth cable
TERMINAL
BLOCK
PCB
TERMINAL
BLOCK
PCB MAIN
PCB MAIN
C8
PCB MAIN
error
Incorrect
connections
(PCB TERMI-
NAL BLOCK -
SMART-MT)
SMART-MT
CC
serial error
Earth cable
PCB
TERMINAL
BLOCK
SMART-MT
Section II :: Installation and maintenance
Check the electrical continu-
ity with a tester [tables].
-------
Check the electrical continu-
ity of FUSE CF2 with a tester
[fig. 2].
Check the voltage of the FAN
MOTOR [fig. 2].
Check the electrical continu-
ity with a tester [tables].
10kW Unit: Check the electri-
cal continuity of FUSE CF6
with a tester [fig. 1].
13-16kW Unit: Check the
electrical continuity of FUSE
CF7 with a tester [fig. 1].
Check the voltage of the FAN
MOTOR [fig. 2].
Check the installation room
(air intake and output clog-
ging).
-------
-------
-------
Check the connection.
-------
Fault is different from the
above cases.
Fault is different from the
above cases.
Disconnect the power supply,
wait for about 3 minutes and
then reconnect it
Check the loosened connec-
tions and the contacts with
the reactors.
Check the connections.
-------
Fault is different from the
above cases.
Fault is different from the
above cases.
50
Solution
Replace the sensor if it is faulty.
Replace the PCB MAIN
If fuse CF7 is blown, replace the FAN MOTOR
and the fuse. If fuse CF6 is not blown, check the
voltage of the FAN MOTOR [fig. 2]. If the voltage
is normal, replace the FAN MOTOR. If the volt-
age is abnormal, replace the PCB MAIN board.
Replace the sensor if it is faulty.
If fuse CF6 or CF7 is blown, replace the FAN
MOTOR and the fuse. If fuse CF6 or CF7 is not
blown, check the voltage FAN MOTOR and the
fuse. If the voltage is normal, replace the FAN
MOTOR. If the voltage is abnormal, replace the
PCB MAIN board.
Correct the installation position to prevent the air
intake and output pipes from clogging.
Replace the PCB MAIN
Replace the PCB MAIN.
Replace the PCB MAIN.
Once the wiring error is corrected, reactivate the
appliance.
Verify that the earth wire has been installed cor-
rectly.
Replace the PCB TERMINAL BLOCK.
Replace the PCB MAIN.
If the same error code appears again, replace the
PCB MAIN.
Check the connection of the wiring and the incor-
rect contact and then restart the appliance.
Verify that the earth wire has been installed cor-
rectly.
Replace the PCB TERMINAL BLOCK.
Replace the SMART-MT.