Channels
Input impedance
Scales
Measurement with current clamps
Sensitivity
POWERS
Single phase power
Total power
POWER COUNTERS
Maximum value before reset
ACCURACY
RMS Voltages:
Scale 1
Scale 2
RMS Currents:
Scale 1
Scale 2
Scale 3
Scale 4
Power
Power Factor (PF)
Frequency
Active power count (kW)
Reactive power count (kVar)
HARMONIC ANALYSIS
ANALYSIS OF EN50160 PARAMETERS
Interruptions
Dips
Swells
TRANSIENT ANALYSIS
Swells and overcurrents
Inrush current analysis
COMUNICATION:
USB
DATA STORAGE:
Internal memory
External memory
OPERATING CONDITIONS:
Operating temperature
Storage temperature
Relative humidity
Maximum altitude a.s.l. (600V CAT III)
EC COMPLIANCE:
Directives
REFERENCE STANDARDS:
Safety
Electromagnetic Compatibility (EMC)
5 independent channels
10KOhm
4
Ratio: 1-60000
Maximum value which can be displayed: 500KA
0,2% of F.S.
Values < 999 GW,Gvar,GVA
Values < 999 GW,Gvar,GVA
99999999 kWh, kvarh, kVAh
(2)
±0,25% + 0,1%FS
(2)
±0,25% + 0,05%FS
(2)
±0,25% + 0,1%FS
(2)
±0,25% + 0,05%FS
(2)
±0,25% + 0,05%FS
(2)
±0,25% + 0,05%FS
(2)
±0,5% + 0,05%FS
±0,5°
±0,01 Hz (40-70Hz)
Class 0,5
Class 1
Up to 50th order
>500mS
>500mS
>500mS
>150uS
RMS continuous sampling every 2 periods. Duration 1, 2, 5, 10 sec
To PC
64kB
Micro SD (8GB included)
from -10 to +55 °C
from -20 to +85 °C
Max 95%
2000 m
93/68/EEC (Low Voltage Electrical Equipment);
89/336/EEC and 2004/108/EC (EMC - Electromagnetic Compatibility);
2006/95/EC - 72/23/EEC (LVD - Low Voltage Directive);
2002/95/EC (RoHS - Restriction of Hazardous Substances);
2002/96/EC and 2003/108/EC (WEEE - Waste Electrical and Electronic
Equipment);
EN 61010-1
EN 61326
EN 61326/A1
EN 61326/A2
- 104 -
(1)
@ V RMS < 350VCA
(1)
@ V RMS > 350VCA
(1)
@ I RMS < 5% IN clamp
@ 5% < I RMS < 20% IN clamp
@ 20% < I RMS < 50% IN clamp
(1)
@ > 50% IN clamp
(1)
(1)