B: No process water supply
possible cause
No power supply
Shut-off valve in the process
water pipe closed
No water in Stage 3
Pressure pump transports no
water
C: Odour / poor process water quality
possible cause
Incorrect installation
System malfunction
Dry siphon in the drainage pipe
of Stage 3
EN 60
Check
Visual inspection:
-
Room and system
fusing
-
Fusing of the system
circuit board
Function check of the
•
drinking water feed in
manual operation (see
chapter 6.7.1)
Check the pressure
•
transmitter
Check whether the pressure
booster system is enabled.
Check
Check of:
"Which water enters the
•
system?"
Separate ventilation of the
•
infeed? (e.g. roof
ventilation)
Odour trap to the sewer at
•
the system drain?
Room ventilation present?
•
Check of the air pumps (see
chapter 7.4.1)
Check of the electric ball valves
(see chapter 7.3)
Dismantle siphon at overflow of
Stage 3
Operating Manual AquaCycle 2500
Remedies
Determine the cause of the
shut-down!
If necessary, re-insert fuse or
replace the circuit board fuse
Open the shut-off valve
Multiple actuation of the drinking
water feed in manual operation
See the Operating Manual of
your pressure booster system.
Remedy
Introduction only of:
Shower and bath water
•
Operation only with separate
ventilation, odour trap and room
ventilation
Cleaning and, if necessary,
replacement of the defective
components by Pontos or a
skilled electrician.
Open the cover above the
drainage pipe on top of the
Stage 3 tank and put water into
the discharge pipe until the
siphon is full.
Version 2.5