EVSE Sub-
Maximum mains current available for load
Distribution Limit
management
(L1/L2/L3) [A]
Operator EVSE
Upper current limit for load management. This
Sub-Distribution
value can be changed during operation (e.g. tem-
Limit (L1/L2/L3) [A]
porarily from Backend-System)
External Input 1
Config
Ext. Input 1 Current
Offset (L1/L2/L3) [A]
External Input 2
Config
Ext. Input 2 Current
Offset (L1/L2/L3) [A]
External Meter
This setting specifies whether an external energy
Support
meter is connected for additional consumers
Main Distribution
Upper current limit for load management and for
Limit (L1/L2/L3) [A]
additional consumers
External Load
Safety margin for volatile consumers (in A).
Headroom (L1/L2/
Subtract this value from the value in the parame-
L3) [A]
ter "Main Distribution Limit (L1/L2/L3) [A]" to obtain
the maximum upper current limit of the charging
infrastructure
External Load
Upper current limit if no external energy meter is
Fallback (L1/L2/L3)
connected
[A]
External Meter
This setting specifies how the external energy
Location
meter is connected
External Load
Setting that specifies the duration (in seconds) to
Averaging Length
be used for determining the average of the exter-
[sec]
nal energy meter
30
Charging
system
Not relevant for the device
Not relevant for the device
Not relevant for the device
Not relevant for the device
Charging
system
e.g. rated fuse current in the
power supply cable
This value is smaller than or
equals the value for "EVSE
Sub-Distribution Limit"
The external energy meter has
to be connected to the rou-
ter or switch via an ethernet
cable.
Î "5.6 Networking devices"
„ Only if "External Meter
Support" = "On"
„ This value is higher than
the value for "EVSE Sub-
Distribution Limit"
Only if "External Meter
Support" = "On"
Only if "External Meter
Support" = "On"
„ Only if "External Meter
Support" = "On"
„ "Including EVSE Sub-
Distribution": Used to detect
charging points and additio-
nal consumers
„ "Excluding EVSE Sub-
Distribution": Used to detect
external consumers only
„ Only if "External Meter
Support" = "On"
„ Preset: "5"