SMA Solar Technology AG
Pin
Signal
3
RD+
6
RD-
Interference of network data transmission due to AC cables
When AC cables are in operation, they generate an electromagnetic field which may induce leading or lagging
interference in network cables during data transmission.
• Lay the network cables using suitable fastening material while observing a minimum clearance of 50 mm to
the AC cables.
Cable requirements:
☐ Conductor cross-section: at least 2 x 2 x 0.22 mm
☐ Cable type: 100BaseTx, at least CAT5e with shielding S/FTP, F/FTP or higher
☐ Cable length for installation cable: maximum 100 m
☐ Cable length for patch cable: maximum 50 m
☐ Cables to be laid outdoors must be UV-resistant or routed in a UV-resistant cable channel.
☐ Type of plug: RJ45
☐ RJ45 plugs used for installation cables must have a metal enclosure. The cable shield must be connected on both
ends of the installation cable.
Requirement:
☐ When connecting the SMA Inverter Manager, the requirements for the internal communication network of the PV
diesel hybrid system must be observed (see Section 6.8.1, page 35).
Procedure:
1. Insert the cable into the Fuel Save Controller (see Section 9.1, page 47).
2. Connect the cable to the router K201 at the pin connector X10.
6.8.6
Connecting the Communication with the Data Acquisition Module via RJ45
Network Cable
You can connect the Fuel Save Controller with an optional Data Acquisition Module using RJ45 network cables. When
you connect the Fuel Save Controller with an Ethernet BASE-T network, always connect the network cables as follows.
Plug assignment:
Figure 17: RJ45 plug assignment
Pin
Signal
1
TD+
Installation Manual
EIA/TIA 568A (8-conductor) con-
ductor color
white/orange
orange
2
or at least 2 x 2 AWG 24
EIA/TIA 568A (8-conductor) con-
ductor color
white/green
6 Electrical Connection
Profinet (4-conductor) conductor
color
white
blue
Profinet (4-conductor) conductor
color
yellow
FSC20-IA-xx-20
39