18
Mechanical release
In the event of a fault or mains power loss, the barrier may be released and opened manually.
For further information, refer to the locking/release operation in the manual of the
automation system BI001/PC, BI/001PE.
If the barrier is unlocked while the controller is powered, the message
again.
The flashing light and the signal lights (if installed) illuminate if the boom is moved manually.
The barrier resumes normal operation once the release system is locked again.
19
Initial testing
The testing must be performed by qualified technical personnel.
The installer is required to measure impact forces and select on the control unit the appropriate
speed and torque values to ensure that the motorised door, gate or barrier remains within the limits
defined by the standards EN 12453 and EN 12445.
Make sure that the provisions in Chapter 1 "GENERIC WARNINGS are observed.
• Turn on the power supply.
• Perform travel acquisition.
• Set the open and close speed settings. Check that the values are correct for the installation type.
The boom must approach the mechanical stop at low speed, and then press gently against the
stop to hold the boom in the closed position. The pressure exerted against the stop is set with
the parameter
.
• Check that all connected controls are working correctly.
• Check that the release device functions correctly. The message
• Check if the impact forces are compliant with the EN 12453 and EN 12445 standards.
• Check that the safety devices are activated correctly.
• If installed, check the correct operation of the BreakAway ACS/BA/60 detachable boom coupling
system.
• If the battery kit is installed, disconnect from mains and check that the batteries are working.
• Disconnect from mains power and disconnect the batteries (if used), then reconnect. With the
barrier stopped in an intermediate position, check that the manoeuvre is performed correctly.
• Check that the mechanical stops are set correctly. Repeat the travel acquisition procedure after
each adjustment.
20
Start-up
The installer is required to draw up and preserve the technical file of the system for at least 10 years, which must contain
the wiring diagram, the drawing and the photo of the system, the risk analysis and the solutions adopted, the manufacturer's
declaration of conformity for all connected devices, the instructions manual of each device and / or accessory and the
system's maintenance plan.
Apply a plate indicating the automation system data on the motorised door, gate or barrier, the name of the person in charge
of the start-up, the serial number and the year of construction, as well as the CE mark.
Apply a plate and / or label with the indications for the operations required to manually unlock the system.
Draw up and provide the end user with the declaration of conformity, instructions and warnings for use and the maintenance
plan.
Make sure that the end user has understood the correct automatic, manual or emergency operation of the system.
Inform the end user about the dangers and risks that may be present.
flashes on the display until the barrier is locked
must flash on the display.
79