Mechanical Installation

WARNING
Fire Hazard. Do not put flammable or combustible materials on top of the drive and do not install the drive
near flammable or combustible materials. Attach the drive to metal or other noncombustible material. Failure to obey can cause
death or serious injury.
CAUTION
Crush Hazard. Do not hold the drive by the front cover or terminal cover. Tighten the screws correctly before
moving the drive. Failure to obey can cause minor to moderate injury.
NOTICE
Do not put drive peripheral devices, transformers, or other electronics near the drive. Shield the drive from
electrical interference if components must be near the drive. Failure to obey can cause incorrect operation.
NOTICE
Do not let unwanted objects, for example metal shavings or wire clippings, fall into the drive during drive
installation and project construction. Put a temporary cover over the top of the drive during installation. Remove the temporary
cover before start-up or the drive will overheat. Failure to obey can cause damage to the drive.
NOTICE
Install the drive as specified by EMC Guidelines. Failure to obey can cause incorrect operation and damage to
electrical devices.
NOTICE
Obey correct electrostatic discharge (ESD) procedures when you touch the drive. Incorrect ESD procedures
can cause damage to the drive circuitry.

Installation Environment

The installation environment is important for the lifespan of the product and to make sure that the drive
performance is correct. Make sure that the installation environment agrees with these specifications.
Environment
Indoors
Area of Use
Overvoltage Category III
Power Supply
IP20 enclosure: -10 °C to +60 °C (14 °F to 140 °F). Derate the output current and output voltage if the drive is installed in areas with ambient
temperatures from +50 °C to +60 °C (122 °F to 140 °F).
UL Type 1 enclosure: -10 °C to +50 °C (14 °F to 122 °F). Derate the output current and output voltage if the drive is installed in areas with ambient
Ambient Temperature
temperatures from +40 °C to +50 °C (104 °F to 122 °F).
Setting
• Drive reliability is better in environments that do not have wide temperature fluctuations.
• When installing the drive in an enclosure, use a cooling fan or air conditioner to keep the internal air temperature in the permitted range.
Humidity
95% RH or less, non-condensing
-20 °C to +70 °C (-4 °F to +158 °F)
Storage Temperature
12
Table 1.2 Drive Modes, Menu Screens and Functions
Menu Screen
Sets monitor items to display.
Auto-Tunes the drive.
Changes initial settings.
Changes application settings.
Changes tuning settings.
Changes reference settings.
Changes motor settings.
Changes external options settings.
Changes terminals settings.
Changes protection settings.
Changes settings for special applications.
Changes keypad settings.
Changes parameters of Q2Pack software.
Changes joints of Q2Pack software.
Function
Conditions
TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions