Low Voltage Wiring For Control Circuit Terminals; Drive Motor Overload And Overheat Protection - Omron Q2 Serie Instrucciones De Instalación Y Funcionamiento

200 v class 0.55 kw to 110 kw, 400 v class 0.55 kw to 315 kw
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than
100,000 RMS symmetrical amperes and 480 Vac when there is a short circuit in the power supply.
The built-in short circuit protection of the drive does not provide branch circuit protection. The user must provide
branch circuit protection as specified by the National Electric Code (NEC), the Canadian Electric Code, Part I
(CEC), and local codes.

Low Voltage Wiring for Control Circuit Terminals

You must provide low voltage wiring as specified by the National Electric Code (NEC), the Canadian Electric
Code, Part I (CEC), and local codes. The NEC class 1 circuit conductor is recommended. Use the UL approved
class 2 power supply for external power supply.
Input/Output
Digital input
Analog input
Analog output
Pulse train output
Pulse train input
Safe disable input
Serial communication input/output
24 V external power supply

Drive Motor Overload and Overheat Protection

The drive motor overload and overheat protection function complies with the National Electric Code (NEC) and
the Canadian Electric Code, Part I (CEC).
Set the Motor Rated Current and L1-01 through L1-04 [Motor Cool Type for OL1 Calc through Motor oH FLT
Reaction Select] correctly to enable motor overload and overheat protection.
Refer to the control method and set the motor rated current with E2-01 [Mot Rated Current (FLA)], E5-03 [PM
Mot Rated Current (FLA)], or E9-06 [Motor Rated Current].
E2-01 Mot Rated Current (FLA)
No.
Name
(Hex.)
E2-01
Mot Rated Current (FLA)
(030E)
Note:
• If E2-01 < E2-03 [Mot No-Load Current] the drive will detect oPE02 [Parameter Range Setting Error].
• The default settings and setting ranges are in these units:
–0.01 A: 2004 to 2042, 4002 to 4023
–0.1 A: 2056 to 2415, 4031 to 4675
The value set for E2-01 becomes the reference value for motor protection, the torque limit, and torque control.
Enter the motor rated current as written on the motor nameplate. The value of E2-01 is automatically set to the
value input for "Motor Rated Current" by the Auto-Tuning process.
TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions
Table 6.4 Control Circuit Terminal Power Supplies
Terminals
DI1-DI8, DIC, D0V, D24V
PI, +10V, -10V, AI1, AI2, AI3, A0V
AO1, AO2, A0V
PO, A0V
PI, A0V
H1, H2, HC
RS485+, RS485-, A0V
E24V, A0V
Sets the motor rated current in amps.
Power Supply Specifications
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external
power supply.
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external
power supply.
Uses the LVLC power supply in the drive.
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external
power supply.
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external
power supply.
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external
power supply.
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external
power supply.
Use the UL Listed class 2 power supply.
Description
6 Attachments
EN
Default
(Range)
Determined by o2-04 and
C6-01
(10% to 200% of the drive
rated current)
125

Publicidad

Tabla de contenido

Solución de problemas

loading

Productos relacionados para Omron Q2 Serie

Este manual también es adecuado para:

Q2a serieQ2a-a serie

Tabla de contenido