Omron Q2 Serie Instrucciones De Instalación Y Funcionamiento página 19

200 v class 0.55 kw to 110 kw, 400 v class 0.55 kw to 315 kw
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Code
Name
oC
Overcurrent
oL1
Motor Overload
TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions
Causes
The load is too heavy.
Overheating caused damage to the motor or the
motor insulation is not satisfactory.
The motor main circuit cable is contacting ground
to make a short circuit.
A short circuit or ground fault on the drive output
side caused damage to the output transistor of the
drive.
The acceleration time is too short.
The drive is trying to operate a specialized motor or
a motor that is larger than the maximum applicable
motor output of the drive.
A magnetic contactor was switched at the output.
The V/f pattern settings are incorrect.
The torque compensation gain is too large.
Electrical interference caused a problem.
The gain during overexcitation operation is too
large.
The drive received a Run command while the motor
was coasting.
The motor code is set incorrectly for PM Control
Methods.
If the drive detects the fault at start or in the low
speed range (10% or less) and n8-57 = 1 [High-
Freq Injection = Enabled] for PM Control methods,
the high frequency injection gain is too high.
The current flowing in the motor is more than the
value set in L8-27 [OverCurr Det Gain] for PM
Control.
The control method is set incorrectly for the motor.
The motor main circuit cable is too long.
Speed search does not complete at start when you
use an induction motor in EZOLV control.
The load is too heavy.
Possible Solutions
• Measure the current flowing into the motor.
• Replace the drive with a larger capacity model if the current
value is more than the drive rated current.
• Decrease the load or replace with a larger drive to prevent
sudden changes in the current level.
Measure the motor insulation resistance, and replace the motor if
there is electrical conduction or unserviceable insulation.
• Examine the motor main circuit cable for damage, and repair
short circuits.
• Measure the resistance between the motor main circuit cable
and the ground terminal. If there is electrical conduction,
replace the cable.
• Make sure that there is not a short circuit in terminal B1 and
terminals U/T1, V/T2, and W/T3. Make sure that there is not a
short circuit in terminals - and terminals U/T1, V/T2, and W/
T3.
• If there is a short circuit, contact the manufacturer or your
nearest sales representative.
• Calculate the torque necessary during acceleration related to
the load inertia and the specified acceleration time.
• Increase the values set in C1-01 [Accel Time 1], C1-03 [Accel
Time 2], C1-05 [Accel Time 3], or C1-07 [Accel Time 4] until
you get the necessary torque.
• Increase the values set in C2-01 [Jerk@Start of Accel], C2-02
[Jerk@End of Accel], C2-03 [Jerk@Start of Decel], and C2-
04 [Jerk@End of Decel] until you get the necessary torque.
• Replace the drive with a larger capacity model.
• Examine the motor nameplate, the motor, and the drive to
make sure that the drive rated current is larger than the motor
rated current.
• Replace the drive with a larger capacity model.
Set the operation sequence to not turn ON or OFF the magnetic
contactor while the drive is outputting voltage.
• Examine the ratios between the V/f pattern frequency and
voltage. Decrease the voltage if it is too high compared to the
frequency.
• Adjust V/f Pattern Parameters E1-04 to E1-10. For motor 2,
adjust E3-04 to E3-10.
Decrease the value set in C4-01 [Trq Comp Gain] to make sure
that the motor does not stall.
Examine the control circuit lines, main circuit lines, and ground
wiring, and decrease the effects of electrical interference.
• Find the time when the fault occurs.
• If the fault occurs at the same time as overexcitation operation,
decrease the value set in n3-13 [OverExcBr Gain] and
consider the motor flux saturation.
• Examine the sequence and input the Run command after the
motor fully stops.
• Set b3-01 = 1 [SpSrch@Start Selection = Enabled] or set H1-
xx = 67, 68 [Speed Srch 1 or 2] to input speed search
commands from the MFDI terminals.
• Enter the correct motor code to E5-01 [PM Mot Code
Selection] as specified by the PM motor.
• For specialized motors, refer to the motor test report and set
E5: PM MOTOR SETTINGS correctly.
• Set E5: PM MOTOR SETTINGS correctly or do Rotational
Auto-Tuning.
• Decrease the value of n8-41 [HFI PoleDet Pgain] in 0.5 unit
increments.
Note:
Set n8-41 > 0.0 for IPM motors.
Correct the value set in L8-27.
Set A1-02 [Control Method] correctly.
Replace the drive with a larger capacity model.
When E9-01 = 0 [Motor Type Selection = IM], set b3-24 = 2
[SpSrch Method Selection = Current Det2].
Decrease the load.
Note:
Reset oL1 when U4-16 [MotorOLEstimate (oL1)] < 100.
1 English
EN
19

Publicidad

Tabla de contenido

Solución de problemas

loading

Productos relacionados para Omron Q2 Serie

Este manual también es adecuado para:

Q2a serieQ2a-a serie

Tabla de contenido