Descargar Imprimir esta página

Franklin Electric SUBDRIVE CONNECT Manual Del Usuario página 27

Ocultar thumbs Ver también para SUBDRIVE CONNECT:

Publicidad

Idiomas disponibles

Idiomas disponibles

Power Circuit and Motor Connections
Drive is suitable for use on a circuit capable of delivering not more than 5000 RMS symmetrical amperes,
250 volts maximum.
Verify that the dedicated branch circuit for the drive is equipped with a properly-sized circuit breaker.
Refer to
"Input (Power) Wire and Fuse Sizing" on page 24
Verify that the power has been shut off at the main breaker.
1.
Feed the motor leads through the opening on the bottom right side of the drive and connect them
to the terminal block positions marked GROUND (Green Ground Wire), Red, Yellow and Black. Tight-
en terminals to 15 in-lbs (1.7 Nm).
2. Feed the 230 VAC power leads through the larger opening on the bottom left side of the drive and
connect them to the terminals marked L1, L2, and GROUND. Tighten terminals to 15 in-lbs (1.7 Nm).
NOTE: These terminals accept wire sizes from 6 to 20 AWG and should be tightened to 15 in-lbs
(1.7 Nm).
for minimum breaker size.
ELECTRICAL INSTALLATION
Power Wiring Connections
27

Publicidad

loading