Descargar Imprimir esta página

Franklin Electric SUBDRIVE CONNECT Manual Del Usuario página 50

Ocultar thumbs Ver también para SUBDRIVE CONNECT:

Publicidad

Idiomas disponibles

Idiomas disponibles

MAINTENANCE
Troubleshooting
Codes
Fault
F F 6 6
Short Circuit
F F 7 7
Overheated
Drive
F F 9 9
Internal PCB
Fault
F F 1 1 2 2
Overvoltage
F F 1 1 4 4
Broken Pipe
F F 1 1 5 5
Phase
Imbalance
F F 1 1 6 6
Ground Fault
F F 1 1 7 7
Inverter
Temperature
Sensor Fault
F F 1 1 8 8
PFC
Temperature
Sensor Fault
F F 1 1 9 9
Communication
Fault
50
Possible Causes
When fault is indicated immediately
after power-up, short circuit caused by a
shorted connection, defective cable,
splice, or motor
Amperage exceeded 25 amps on DC test
at start or SF amps during running
Incorrect output wiring, phase to phase
short, phase to ground short in wiring or
motor
High ambient temperature
Direct sunlight
Obstruction of airflow channel
Fan blocked or inoperable, ambient
above 122 °F (50 °C)
A fault was found internal to drive
High line voltage
Internal voltage too high
Broken pipe or large leak is detected in
the system
Drive runs at full power for 10 minutes
without reaching pressure setpoint
Large water draw, such as a sprinkler
system, does not allow system to reach
pressure setpoint
Motor phase currents differ by 20% or
more.
Motor is worn internally
Motor cable resistance is not equal
Incorrect motor type setting (single- or
three-phase)
Motor output cable is damaged or ex-
posed to water
Phase to ground short
Internal temperature sensor is
malfunctioning
Cable connection between Control Board
and Power Board is loose or
disconnected
Internal circuit failure
Corrective Action
Check wiring and fix as necessary
If fault is present after resetting and removing mo-
tor leads, replace drive
Wait until drive temperature drops below 194 °F (90
°C) to restart
Replace fans or fan module; or relocate drive as
necessary
Remove debris from fan intake/exhaust
Remove and clean optional air screen kit (if
installed)
Contact your Franklin Electric Service Personnel
Unit may require replacement. Contact your
supplier.
Check incoming power connections and correct or
tighten terminals if necessary
If line voltage is stable and measured below 260
VAC and problem persists, contact your Franklin
Electric Service Personnel.
Check system for large leak or broken pipe
If the system contains a sprinkler system or is being
used to fill a pool or cistern, disable the Broken Pipe
Detection.
Check resistance of motor cable and motor
windings.
Verify motor type matched drive settings (single- or
three-phase)
Check motor cable insulation resistance with megger
(while not connected to drive). Replace motor cable
if needed.
Contact your Franklin Electric Service Personnel
If problem persists, unit may require replacement.
Contact your supplier.
Check cable connection between Display/Wi-Fi
Board and Main Control Board.
If problem persists, unit may require replacement.
Contact your supplier.

Publicidad

loading