Descargar Imprimir esta página

Franklin Electric SUBDRIVE CONNECT Manual Del Usuario página 53

Ocultar thumbs Ver también para SUBDRIVE CONNECT:

Publicidad

Idiomas disponibles

Idiomas disponibles

Symptom Based Troubleshooting
Display
Condition
None
Green
"—"
No water
Red Fault
Codes
Green
Motor
Frequency
Pressure
Green
Fluctuations
Motor
(Poor
Frequency
Regulation)
Run On
Green
(pump won't
Motor
stop)
Frequency
Runs But
Flashing
Trips
Red
Possible Cause
No supply voltage present
Display board cable discon-
nected or loose
Pressure sensor circuit
Fault detected
Incorrect motor or pump
settings
Loose switch or cable
connection
Motor may be running
backwards
Gulping water at pump
inlet
Frequency max and amps
high
Frequency max and amps
erratic with dragging
impellers
Pressure sensor placement
and setting
Pressure gauge placement
Pressure tank size and
precharge
Tank may be too small for
system flow
Leak in system
Air in pump intake (lack of
submergence)
System response setting
Pressure sensor placement
and setting
Tank pre-charge pressure
Impeller damage
Leaky system
Sized improperly (pump
can't build enough head)
A fault has occurred
Corrective Action
Verify cable connection between Power Board and Control Board
If correct voltage is present, replace drive
Verify water pressure is below system set point
If Pressure Input Board break-away tab is removed, ensure auxili-
ary device is connected and closed circuit
Jumper wires together at pressure sensor; if pump starts, replace
sensor
If pump doesn't start, check sensor connection at Pressure Input
Board; if loose, repair
If pump doesn't start, jumper sensor connection at Pressure Input
Board. If pump starts, replace wire
If pump doesn't start with sensor Pressure Input Board connec-
tion jumpered, replace Pressure Input Board
If pump doesn't start with new Pressure Input Board, replace
Refer
to"Diagnostic Fault Codes" on page 49
Verify Maximum Frequency setting. If this setting was reduced
below maximum value, increase
Verify motor/pump ratings and match to motor/pump settings
on drive (DIP switch or Wi-Fi)
Verify motor connections
Frequency max, amps low, check for closed valve, or stuck check
valve
Check all piping connections
Disconnect power, allow well to recover, and restart
Check for hole in pipe
Check pump operation and for dragging impellers
Correct pressure sensor placement and settings
Disconnect power and check pressure gauge for drop
Set deeper in the well or tank. Install a flow sleeve with airtight
seal around drop pipe and cable
If fluctuation is only on branches before sensor, enable Steady
Flow
Change tank size configuration
Reduce frequency output range
Adjust System Response value
Check frequency at low flows. Pressure setting may be too close
to pump max head
Verify precharge at 70% if tank size is larger than minimum. In-
crease precharge (up to 85%).
Verify that the system will build and hold pressure
Enable bump and/or aggressive bump
Increase minimum frequency
Proceed to fault code description and remedy
MAINTENANCE
Troubleshooting
.
53

Publicidad

loading