1. B B u u i i l l t t - - I I n n D D u u p p l l e e x x A A l l t t e e r r n n a a t t o o r r : : Use the ALTERNATOR terminals to connect two drives in a lead/lag
configuration. Refer to
tor communication for this connection. Refer to
a. Connect the black cable lead to the A terminal on both drives.
b. Connect the red cable lead to the B terminal on both drives.
c. Connect the green cable lead to the GROUND terminal when applicable.
IMPORTANT: Both drives should be wired from the same panel to ensure proper communication
and operation.
2. M M o o i i s s t t u u r r e e S S e e n n s s o o r r : : The WET SENSOR terminal supports the Franklin Electric Moisture Sensor.
a. Connect the red cable lead to the +24 terminal.
b. Connect the black cable lead to the GROUND terminal.
c. Connect the white cable lead to the I+ terminal.
d. Connect the green cable lead to the I– terminal.
Refer to
"Moisture Sensor" on page 37
"Duplex Alternator Feature" on page
"Accessories" on page
for more information about configuring this input.