MAINTENANCE
Troubleshooting
Codes
Fault
F F 4 4 4 4
Duplex
Alternator
Unexpected
Comm
F F 4 4 5 5
Duplex
Alternator
Demand
Fault
Power down, disconnect leads to the motor and power up the SubDrive:
If the SubDrive does not give an "open phase" fault (F5), then there is a problem with the SubDrive.
Connect the SubDrive to a dry motor. If the motor goes through DC test and gives "underload" fault
(F1), the SubDrive is working properly.
52
Possible Causes
Duplex Alternator cable is installed but
Duplex Alternator function is only con-
figured on one drive
Drives are incorrectly configured
Both drives are running and unable to
satisfy the Primary Setpoint pressure
Corrective Action
Complete Duplex Alternator configuration on both
drives
Ensure both drives are configured properly. One
drive must be configured as Pump 1, the other drive
must be configured as Pump 2, and the Switching
Interval must match.
Inspect each system for proper pump operation