C1448, C1848, C2148
Remote Condenser Models - Installation Manual
Remote Condenser Location
Use the following for planning the placement of the
condenser relative to the ice machine
Location Limits - condenser location must not
exceed ANY of the following limits:
•
Maximum rise from the ice machine to the
condenser is 10 meters
•
Maximum drop from the ice machine to the
condenser is 4 and half meters
•
Physical line set maximum length is 30
meters.
•
Calculated line set length maximum is 45.
Calculation Formula:
•
Drop = dd x 2 (dd = distance in meters)
•
Rise = rd x 1.2 (rd = distance in meters)
•
Horizontal Run = hd x 1 (hd = distance in
meters)
•
Calculation: Drop(s) + Rise(s) + Horizontal
Run = dd+rd+hd = Calculated Line Length
Max 10
meters
hd
Max 4.5
meters
rd
Do NOT:
•
Route a line set that rises, then falls, then
rises.
•
Route a line set that falls, then rises, then
falls.
Calculation Example 1:
The condenser is to be located 2 meters below the
ice machine and then 6 meters away horizontally.
2 x 2 = 4. 4 + 6= 10. This location would be
acceptable
Calculation Example 2:
The condenser is to be located 10 meters above
and then 36 meters away horizontally. 10 x 1.2 =
12. 12 + 36 = 48. 48 is greater than the 45
maximum and is NOT acceptable.
40.35"
dd
Remote Condenser Located
ABOVE Ice Machine
Remote Condenser Located
BELOW Ice Machine
June 2007
Page 8
Condenser Distance &
Location Schematic