"Linear with Stop" and "Linear with Min."
– "Linear with Stop"
In the input signal range from 20 to 100 %, the setpoint is
influenced linearly.
If the input signal is below 10 %, the pump changes to
operating mode "Stop".
If the input signal is increased above 15 %, the operating
mode is changed back to "Normal".
See fig. 62.
– "Linear with Min.".
In the input signal range from 20 to 100 %, the setpoint is
influenced linearly.
If the input signal is below 10 %, the pump changes to
operating mode "Min.".
If the input signal is increased above 15 %, the operating
mode is changed back to "Normal".
See fig. 62.
"Setpoint influence" [%]
100
0
0
20
0.5
0
0
0
4
-50
"Normal"
"Min." or
"Stop"
Fig. 62 "Linear with Stop" and "Linear with Min."
•
"Inverse function".
The setpoint is influenced inversely from 0 to 100 %. See fig.
63.
"Setpoint influence" [%]
100
0
0
0.5
0
0
0
4
-50
Fig. 63 "Inverse function"
46
External
100 %
3.5 V
input
5 V
10 V
20 mA
20 mA
204 C
External
100 %
3.5 V
input
5 V
10 V
20 mA
20 mA
204 C
•
"Inverse with Stop" and "Inverse with Min.".
– "Inverse with Stop"
In the input signal range from 0 to 80 %, the setpoint is
influenced inversely.
If the input signal is above 90 %, the pump changes to
operating mode "Stop".
If the input signal is reduced below 85 %, the operating
mode is changed back to "Normal".
See fig. 64.
– "Inverse with Min.".
In the input signal range from 0 to 80 %, the setpoint is
influenced inversely.
If the input signal is above 90 %, the pump changes to
operating mode "Min.".
If the input signal is reduced below 85 %, the operating
mode is changed back to "Normal".
See fig. 64.
"Setpoint influence" [%]
100
0
0
0.5
0
0
0
4
-50
"Normal"
"Min." or
"Stop"
Fig. 64 "Inverse with Stop" and "Inverse with Min."
External
80
100 %
3.5 V
input
5 V
10 V
20 mA
20 mA
204 C