"Influence table".
The setpoint is influenced by a curve made out of two to eight
points. There is a straight line between the points and a
horizontal line before the first point and after the last point.
"Setpoint influence" [%]
100
0
0
0.5
0
0
0
4
-50
Fig. 65 "Influence table" (example with five points)
"Influence table with Stop at Min.".
The setpoint is influenced by a curve made out of two to eight
points. There is straight line between the points and a
horizontal line before the first point and after the last point. If
the input signal is below 10 %, the pump changes to operating
mode "Stop". If the input signal is increased above 15 %, the
operating mode is changed back to "Normal". See fig. 66.
"Setpoint influence" [%]
100
0
0
20
0.5
0
0
0
4
-50
"Normal"
"Min." or
"Stop"
Fig. 66 "Influence table with Stop at Min." (example with five
points)
External
100 %
input
3.5 V
5 V
10 V
20 mA
20 mA
204 C
External
100 %
3.5 V
input
5 V
10 V
20 mA
20 mA
204 C
"Influence table with Stop at Max.".
The setpoint is influenced by a curve made out of two to eight
points. There is a straight line between the points and a
horizontal line before the first point and after the last point. If
the input signal is above 90 %, the pump changes to operating
mode "Stop". If the input signal is reduced below 85 %, the
operating mode is changed back to "Normal". See fig. 67.
"Setpoint influence" [%]
100
0
0
0.5
0
0
0
4
-50
"Normal"
"Min." or
"Stop"
Fig. 67 "Influence table with Stop at Max." (example with five
points)
Factory setting
See section
10. Technical
data.
External
80
100 %
3.5 V
input
5 V
10 V
20 mA
20 mA
204 C
47