Multicheck6010
Figure 4 10: Example of Low current continuity measurement result
Displayed result:
R
Low current continuity resistance result
I
Current used in the measurement
Warning:
• Low current continuity measurement should only be performed on de-energized objects!
Notes:
• If a voltage of higher than 10 V exists between test terminals, the continuity measurement will not
be performed.
• Before performing a continuity measurement, compensate for the test lead resistance (if
necessary). The compensation is performed in Continuity sub- function R LowΩ.
4.3 Testing RCDs
When testing RCDs, the following sub-functions can be performed:
• Contact voltage measurement,
• Trip-out time measurement,
• Trip-out current measurement,
• RCD autotest.
In general, the following parameters and limits can be set when testing RCDs:
• Limit contact voltage,
• Nominal differential RCD trip-out current,
• Multiplier of nominal differential RCD trip-out current,
• RCD type,
• Test current starting polarity.
- 67 -