4.3.3 Trip-out current
How to perform trip-out current measurement
Step 1
Select the RCD function FCT key and select the Ramp mode with the ▲▼ and ◀▶
navigation keys. The following menu will be displayed:
Step 2
By using cursor keys the following parameters can be set in this measurement:
I
•
: Nominal residual current
ΔN
•
Type: RCD type
Pol.: Test current starting polarity
•
Step 3
Connect the test leads to the instrument and follow the connection diagram shown in
figure 4.12 (see the chapter 4.3.1 Contact voltage) to perform trip- out current
measurements.
Step 4
Check for any warnings and check the online voltage/terminal monitor on the display
before starting the measurement. If everything is ok and the
TEST key. After performing the measurement, the results appear on the display
TEST key. After performing the measurement, the results appear on the display
together with the
Figure 4 17: Example of trip-out current measurement result
Figure 4 16: Trip-out current measurement menu
or
indication.
- 71 -
EN
is shown, press the