Multicheck6010
RCD test current selection (r.m.s. value calculated to 20 ms) according to IEC 61009:
½xIΔN
IΔN (mA)
AC
A
10
5
3,5
30
15
10,5
100
50
35
300
150
105
500
250
175
650
325
228
1000
500
350
*) not available
6.3.2 Contact voltage
Measuring range according to EN61557-6 is 3.0 V ÷ 49.0 V for limit contact voltage 25 V.
Measuring range according to EN61557-6 is 3.0 V ÷ 99.0 V for limit contact voltage 50 V.
Range (V)
3.0 ÷ 9.9
10.0 ÷ 99.9
Test current
Limit contact voltage
6.3.3 Trip-out time
Complete measurement range corresponds to EN61557-6 requirements. Specified accuracies
are valid for complete operating range.
Range (ms)
0.0 ÷ 500.0
Test current
½xIΔN, IΔN, 2xIΔN, 5xIΔN
Multipliers not available see test current selection table
6.3.4 Trip-out current
Measurement range corresponds to EN61557-6 requirements. Specified accuracies are valid for
complete operating range.
Range I
Δ
0.2xIΔN ÷ 1.1xIΔN (AC type)
0.2xIΔN ÷ 1.5xIΔN (A type, IΔN≥30 mA)
0.2xIΔN ÷ 2.2xIΔN (A type,IΔN=10 mA)
0.2xIΔN ÷ 2.2IΔN (B type)
1xIΔN
B
AC
A
B
5
10
20
20
15
30
42
60
50
100
141
200
150
300
424
600
250
500
707 1000 1000 1410
325
650
919 1300 1300
500 1000 1410
*)
Resolution (V)
0.1
0.1
0.5xIΔN
25 V, 50 V
Resolution (ms)
0.1
2xIΔN
AC
A
B
AC
20
40
40
50
60
84
120
150
200
282
400
500
600
848
*)
1500
*)
2500
*)
*)
*)
2000
*)
*)
*)
Accuracy
(-0 % / +10 %) of reading + 5 digits
(-0%/+10%) of reading
Accuracy
±3 ms
Resolution I
Δ
0.05xIΔN
0.05xIΔN
0.05xIΔN
0.05xIΔN
- 88 -
5xIΔN
RCD IΔ
A
B
AC
100
100
212
300
707 1000
*)
*)
*)
*)
*)
*)
*)
*)
Accuracy
±0.1xIΔN
±0.1xIΔN
±0.1xIΔN
±0.1xIΔN
EN