Lower the unit carefully and fix it into place. During handling be careful
not to trap any parts of the body, in order to eliminate any possible risk
of crushing or any other injury if the load drops or shifts suddenly.
II.4.2.1 Handling guidelines
DANGER!
An off-centred barycentre could cause sudden and
hazardous movements. Movement of the unit must
be performed with care, in order to avoid damage to
the external structure and to the internal
mechanical and electrical components. Also make
sure that there are no obstacles or people along the
route, in order to prevent the risk of impact,
crushing or tipping the lifting device.
Y
Model
EWMIG
EWMIG
EWMIG P1-P2
EWMIG P1-P2
EWMIG ASP1-ASP2
EWMIG ASP1-ASP2
II.4.3
STORAGE CONDITIONS
The units cannot be stacked. The temperature limits for storage are
-20÷60°C.
II.5

INSTALLATION INSTRUCTIONS

DANGER!
Installation must only be carried out by skilled
technicians, qualified for working on air
conditioning and refrigeration systems. Incorrect
installation could cause the unit to run badly, with a
consequent deterioration in performance.
DANGER!
The unit must be installed according to national or
local standards in force at the time of installation.
The documentation for accessories supplied loose
included with each kit.
DANGER!
The machine is designed for outdoor installation.
Segregate the unit if installed in areas accessible to
persons under 14 years of age.
DANGER!
Some internal parts of the unit may cause cuts. Use
suitable personal protective equipment.
X
ON
X
Y
X
Y
mm
535
1000
mm
535
1000
mm
535
1000
mm
535
1000
mm
535
900
mm
535
900
35
SECTION II: INSTALLATION AND MAINTENANCE
DANGER!
When the outdoor temperature is around zero, the
water normally produced during the coil defrosting
could form ice and make the flooring near the unit
installation area slippery.
If the unit is not fixed to anti-vibration mounts (KSA), once it has been
set on the ground, it must be firmly bolted down to the floor using M12
metric threaded bolts. Slots are provided in the base for this purpose.
II.5.1
INSTALLATION SITE REQUIREMENTS
The installation site should be chosen in accordance with the provisions
of Standard EN 378-1 and in keeping with the requirements of Standard
EN 378-3. When selecting the installation site, risks posed by accidental
refrigerant leakage from the unit should also be taken into consideration.
II.5.1.1
Outdoor installation
Machines designed for outdoor installation must be positioned so as to
avoid any refrigerant gas leakage entering the building and posing a
hazard to people's health.
If the unit is installed on terraces or building roofs, adequate safety
measures must be taken in order to ensure that any gas leaks cannot
enter the building through ventilation systems, doors or similar
openings.
In the event that the unit is installed inside a walled-in structure (usually
for aesthetic reasons), these structures must be suitably ventilated in
order to prevent the formation of dangerous concentrations of
refrigerant gas.
II.5.2
CLEARANCE AND POSITIONING
IMPORTANT!
Before installing the unit, check the noise limits
allowed in the place where it will be used.
IMPORTANT!
The unit should be positioned to comply with the
minimum recommended clearances, bearing in
mind the access to water and electrical
connections.
The unit is designed for outdoor installation. The unit must be installed
in compliance with the minimum recommended technical spaces,
bearing in mind the access to the water and electrical connections.