Mitsubishi Electric Ecodan EHST20 serie Para El Instalador página 47

Ocultar thumbs Ver también para Ecodan EHST20 serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 242
5
System Set Up
Operation settings
1.
 T oaccesstheOperationsettingsmenuuseF1andF2buttonstoscroll
throughtheservicemenuuntilOperationsettingsishighlighted.
2.
PressCONFIRM.
3.
Operationsettingsmenuisdisplayed.
<Freeze stat function>
1.
FromtheAuxiliarysettingsmenuhighlightFreezeStatFunction.
2.
PressCONFIRM.
3.
Thefreezestatfunctionscreenwillbedisplayed.
4.
 U sebuttonsF3andF4toadjusttheminimumoutdoorambienttemperature
whichfreezestatfunctionwillbegintooperate,(3-20°C)orchoose .
  I fasterisk( )ischosenfreezestatfunctionisdeactivated.(i.e.primarywater
freezerisk)
Note: When the system is turned off, freeze stat function is not enabled.
<Simultaneous Operation>
Forperiodsofverylowoutsidetemperaturethismodecanbeused.
SimultaneousoperationallowsbothDHWandspaceheatingtoruntogetherby
usingtheheatpumpand/orboosterheatertoprovidespaceheatingwhilstonly
theimmersionheaterprovidesheatingforDHW.Thisoperationisonlyavailable
ifBOTHaDHWtankANDimmersionheaterarepresentonthesystem.
1.
 F romtheOperationsettingsmenuuseF1andF2buttonstoscrollthroughthe
listuntilSimultaneousoperationishighlighted.
2.
PressCONFIRM.
3.
Simultaneousoperationscreenisdisplayed.
4.
ToswitchsimultaneousoperationON/OFFpressF1.
5.
ToalterthetemperatureatwhichsimultaneousoperationstartsuseF3andF4.
Note:
Range of outdoor ambient temperature is −15°C to 10°C (default −15°C).
System shall automatically return to routine operation. This will happen
when the outdoor ambient temp rises above the selected temp for this
specific mode of operation.
<Cold weather function>
Forextremelylowoutdoorambienttemperatureconditionswhentheheatpump's
capacityisrestrictedtheheatingorDHWisprovidedonlybytheelectricbooster
heater(andimmersionifpresent).Thisfunctionisintendedforuseduring
extremecoldperiodsonly.ExtensiveuseofdirectelectricalheatersONLYwill
resultinhigherelectricusageandmayreduceworkinglifeofheatersandrelated
parts.
1.
 F romtheOperationsettingsmenuuseF1andF2buttonstoscrollthroughthe
listuntilColdweatherfunctionishighlighted.
2.
PressCONFIRM.
3.
Coldweatherfunctionscreenisdisplayed.
4.
ToswitchColdweatherfunctionON/OFFpressF1.
5.
 T oalterthetemperatureatwhichheaterswitchingfunctionstartsuseF3and
F4.
Note:
Range of outdoor ambient temperature is −15°C to −10°C (default −15°C).
System shall automatically return to routine operation. This will happen
when the outdoor ambient temp rises above the selected temp for this
specific mode of operation.
Operationsettingsmenuscreen
Freezestatfunctionscreen
Simultaneousoperationscreen
Coldweatherfunctionscreen
46

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido