Menu 1: Control parameters
No.
Description
Peak-load pump 1 off
1.2.2.4
Value range: 0.06 ... 12.42
Factory setting: 0.50
Peak-load pump 2 on
1.2.2.5
Value range: 0.09 ... 12.45
Factory setting: 1.00
Peak-load pump 2 off
1.2.2.6
Value range: 0.06 ... 12.42
Factory setting: 0.75
Peak-load pump 3 on
1.2.2.7
Value range: 0.09 ... 12.45
Factory setting: 1.25
Peak-load pump 3 off
1.2.2.8
Value range: 0.06 ... 12.42
Factory setting: 1.00
Delay times for activation and deacti-
1.2.5.0
vation of the pumps
Base-load pump stop delay
1.2.5.1
Value range: 0 ... 60
Factory setting: 5
Peak-load pump(s) activation delay
time
1.2.5.2
Value range: 1 ... 30
Factory setting: 3
Peak-load pump(s) stop delay
1.2.5.3
Value range: 0 ... 30
Factory setting: 1
Stop delay at dry-running level
1.2.5.4
Value range: 0 ... 10
Factory setting: 0
Activation delay time after dry run
1.2.5.5
Value range: 0 ... 10
Factory setting: 1
System activation delay time after
power interruption
1.2.5.6
Value range: 0 ... 180
Factory setting: 0
Menu 2: Communication parameters
No.
Description
2.0.0.0 Communication
Field bus
2.1.0.0
Values: None, Modbus, BACnet, GSM
Factory setting: None
Menu 3: Pump activation
No.
Display
3.0.0.0 Pump activation
Switching automatic mode on/off
3.1.0.0
Values: ON, OFF
Factory setting: OFF
3.2.0.0. Operating mode per pump
3.2.x.0 Selection of pump 1 ... 4
Operating mode, pump 1
3.2.1.1
Values: OFF, HAND, AUTO
Factory setting: AUTO
Operating mode, pump 2
3.2.2.1
Values: OFF, HAND, AUTO
Factory setting: AUTO
Operating mode, pump 3
3.2.3.1
Values: OFF, HAND, AUTO
Factory setting: AUTO
Operating mode, pump 4
3.2.4.1
Values: OFF, HAND, AUTO
Factory setting: AUTO
Menu 4: Display of current settings and basic switchgear data
No.
4.1.0.0 Current operating values
4.1.1.0 Current level
4.1.2.0 Current control values
4.1.2.1 Base-load pump on
4.1.2.2 Base-load pump off
4.1.2.3 Peak-load pump 1 on
4.1.2.4 Peak-load pump 1 off
4.1.2.5 Peak-load pump 2 on
4.1.2.6 Peak-load pump 2 off
4.1.2.7 Peak-load pump 3 on
4.1.2.8 Peak-load pump 3 off
Display
4.1.4.0 Limit values
4.1.4.1 Dry-running protection level
4.1.4.2 High water alarm level
4.2.0.0 Operating data
4.2.1.0 Total running time of the system
4.2.2.x Running time of the individual pumps
44
Description
Description
Display