Hitecsa RCAH RCF Serie Manual De Instalación, Operación Y Mantenimiento página 78

Recuperadores de calor con circuito frigorífico integrado
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

9 – T
ROUBLESHOOTING
Guidelines for troubleshooting
The following table lets the User make a first rough check when one of these possible failures are detected in the plant
system; to check and solve alarm situations shown by the controller on the remote control panel display please consult the
controller manual.
Detected failure
Fans not running
Compressor not running
Insufficient air volume
Insufficient heating/cooling capacity
Too frequent defrost mode
Too high condensing pressure
Condensed water stays inside
10 – M
D
ATERIAL
At the end of its lifetime, each unit shall be disposed complying with the regulations in force in the country where it has
been installed.
The main materials used are:
Prepainted sheet metal
-
Galvanized sheet metal
-
-
Aluminum sheet metal
Copper
-
Polyester
-
-
Mineral wool
Plastic
-
Power supply
Fan control signal
Electrical
loosened
Motors overloaded or on alarm
condition
Compressor working point out of
envelope (too high condensing
pressure/too low evaporating
pressure/too low speed)
Motor overloaded
Air filter(s) dirty
Air ducts not clear
Fan settings inadequate
Refrigerant filling too low
Temperature setpoint not compatible
with actual system working condition
Fresh air temperature too low
Return air temperature too low
Exhaust airflow rate too low
Exhaust airflow rate too low
Air inlet temperature(s) too high
Refrigerant filling too high
Drainage point not clear
Drain trap missing or not proper
ISPOSAL
Possible why
missing
missing
connections
wrong
What to do
Switch on main power supply/unit
Check fan settings/fan signal
or
Restore the right connections
Check the input current/check fan
settings
Check airflow rates, indoor and
outdoor air conditions, supply air
temperature setpoint and compare
them to unit limits; too low capacity
required
Too much capacity required
Replace filter(s)
Check ductwork (dampers open ?)
Check fan settings
Contact service center
Check the setpoint and the actual
working condition
Preheat fresh air
Wait for the right room temperature
before starting the unit
Check return air filter and return air
circuit pressure drop
Check return air filter and return air
circuit pressure drop
Check the actual working condition
comparing to unit limits
Contact service center
Clean and clear the drainage point
Install proper drain trap
9

Publicidad

Tabla de contenido
loading

Tabla de contenido