Gas Firing - Cuenod C 75 Instrucciones De Montaje

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Start up
Working cycle test
Firing gas
GAS working cycle test
FUEL OIL valves must be closed
· Open, then immediately reclose fuel
quarter-turn hand-operated valve.
· Switch burner on.
· Select, on burner control panel TC,
gas manual operating mode
S1/H10.1 - S29J - S2K - S4.
· Close thermostatic circuit.
· Open the control and safety unit and
check if it is working correctly.
Program sequence should be as
follows:
complete opening of the air flap,
preventilation for 30s,
return to ignition position,
electrodes ignition for 6s,
valves open,
valves close no more than 3s after
opening,
burner stops due lack of gas
pressure or control and safety unit
locks because flame goes out.
If a doubt arises, repeat the above
test.
Unit can only be fired once this very
important working cycle test has been
performed.
Firing
m
Warning:
Unit may be only fired when all
the requirements listed in
previous sections have been met.
Notably, choice of priority fuel
(fuel oil).
· Connect a microammeter (0-500µA
DC scale) instead of measuring
bridge found under TC.
m
Respect the direction of
connection.
· Close FUEL OIL valves.
· Open GAS valves.
· Close thermostatic circuit.
· Release control and safety unit.
Burner is in operation.
· Check the following :
combustion as soon as flame
appears,
any possible gas manifold leaks.
No leaks should be observed.
· Read cell current (value set from
200 to 500µA).
· Measure gas flow at meter.
· Increase power to nominal flow-rate
by pressing S3+ pulse switch.
· Check combustion.
Comply with recommended boiler
manufacturer smoke temperature
value, in order to obtain the required
effective output.
According to combustion value, with
burner working at nominal rate, turn
screw V on valve MB VEF, or screw R
of SKP regulator.
· To increase CO
rate, increase the
2
ratio and vice versa.
· Read cell current (value set from
200 to 500µA).
· Measure gas flow at meter.
· Increase or reduce power by
increasing or reducing value read on
cam I graduated cylinder.
· Stop, then restart burner.
· Check combustion as soon as flame
appears.
According to measured values, with
burner in operation, turn screw N on
valve MB VEF, or screw D of SKP
regulator.
· If required, adjust cam III value.
· Increase power to min. regulation
flow.
· Check combustion.
· Adjust air/gas flow via cam V for
min. regulation. Setting is performed
in the same way as for cam I.
· Return power to nominal flow and
check combustion parameters. If
value has changed after turning
screw N (screw D for SKP), adjust
ratio V (screw R for SKP) as
appropriate.
06/2006 - Art. Nr. 13 013 497B
m
Important: do not reset
dimension Y, if FUEL OIL has
been set, otherwise :
· Optimize combustion results by
adjusting dimension Y secondary air,
according to procedure described in
the " Setting combustion and
secondary air components " section.
· Reduce dimension Y, CO
2
increases and vice versa.
Any dimension Y modification may
require adjusting secondary air.
· Check combustion.
Check operation during the following:
firing, increasing and decreasing
power.
· While burner is in operation and
using foam designed for that
purpose, check for any possible
leaks in gas manifold connections.
No leaks should be observed.
· Check safety units.
index
EN
45

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

C 100

Tabla de contenido