Français
The total available current from the digital output plus the +24V output is 100mA.
NOTE
B4
Digital Input - Enable/Reset*/**
B5
Digital Input - Run Forward**
B6
Digital Input - Run Reverse**
B7
Digital Input - Local/Remote speed reference select (A1/A2)
Logic
Voltage range
Nominal threshold voltage
If the enable terminal is opened, the drive's output is disabled and the motor will coast to
a stop. The drive will not re-enable for 1.0s after the enable terminal is closed again.
*Following a drive trip, opening and closing the enable terminal will reset the drive. If the
run forward or run reverse terminal is closed, the drive will run straight away.
**Following a drive trip and a reset via the stop/reset key, the enable, run forward or run
reverse terminals will need to be opened and closed to allow the drive to run. This
ensures that the drive does not run when the stop/reset key is pressed.
The enable, run forward and run reverse terminals are level triggered apart from after a
trip where they become edge triggered. See * and ** above.
If the enable and run forward or enable and run reverse terminals are closed when the
drive is powered up, the drive will run straight away up to a set speed.
If both the run forward and run reverse terminals are closed, the drive will stop under the
control of the ramp and stopping modes set in Pr 30 and Pr 31.
Digidrive SK Getting Started Guide
Issue Number: a
English
Deutsch
Italiano
Positive logic only
0 to +24V
+10V
Español
61