Function
13
Not used
14
No
Function
15
Jog reference
Defines the jog speed
No
Function
16
Analog input 1 mode
Determines the input on terminal T2
0-20: Current input 0 to 20mA (20mA full scale)
20-0: Current input 20 to 0mA (0mA full scale)
4-20: Current input 4 to 20mA with current loop loss (cL) trip (20mA full scale)
20-4: Current input 20 to 4mA with current loop loss (cL) trip (4mA full scale)
4-.20:Current input 4 to 20mA with no current loop loss (cL) trip (20mA full scale)
20-.4:Current input 20 to 4mA with no current loop loss (cL) trip (4mA full scale)
VoLt: 0 to 10V input
In the 4-20 or 20-4mA modes (with current loop loss) the drive will trip on cL1 if the input
NOTE
reference is below 3mA. Also, if the drive trips on cL1, the voltage analog input cannot
be selected.
If both analog inputs (A1 and A2) are to be set-up as voltage inputs, and if the
NOTE
potentiometers are supplied from the drive's +10V rail (terminal T3), they must have a
resistance >4kΩ each.
No
Function
17
Enable negative preset speeds
OFF:Direction of rotation controlled by run forward and run reverse terminals
On: Direction of rotation controlled by preset speed values (use run forward terminal)
No
Function
18
Preset speed 1
19
Preset speed 2
20
Preset speed 3
21
Preset speed 4
Defines preset speeds 1 to 4.
No
Function
22
Load display units
Ld: Active current as a % of motor rated active current
A: Drive output current per phase in A
No
Function
23
Speed display units
Fr: Drive output frequency in Hz
SP: Motor speed in rpm
Cd: Machine speed in customer defined units (See Pr 24).
72
English
Deutsch
0-20, 20-0, 4-20, 20-4,
4-.20, 20-.4, VoLt
OFF (0) or On (1)
(Limited by setting of Pr 02
Maximum set speed)
Italiano
Range
Range
0 to 400.0 Hz
Range
Range
Range
±1500 Hz
Range
Ld, A
Range
Fr, SP, Cd
Digidrive SK Getting Started Guide
Español
Defaults
Type
Defaults
Type
1.5
RW
Defaults
Type
4-.20
RW
Defaults
Type
OFF (0)
RW
Defaults
Type
0
RW
Defaults
Type
Ld
RW
Defaults
Type
Fr
RW
Issue Number: a