6.4.3 Control of voltage and frequency
Control that the voltage and frequency levels required by
the generating set correspond to the generator data plate.
The generator leaves the production line
with a star connection (unless otherwise
!
specifi ed on order) which is used as
WARNING!
reference for its nominal data.
All changes in connection must be carried
out solely by a qualifi ed specialist.
!
WARNING!
6.4.4 AVR board settings
The various generator parameters are
!
factory set before testing: so no further
adjustments on the machine should be
WARNING!
necessary; in the event that the covers
need to be removed for the adjustments and live
electrical con tacts are left bare, it is important that
this operation be carried out solely by qualifi ed
specialists in electrical plant maintenance.
The regulator AVR DBL1 uses a microprocessor for
adjustment of generators 50/60 Hz brushless. The voltage
regulation is done by controlling the current in the stator
exciter
6.4.4.1 Characteristics of regulator
•
Automatic adjustment of the voltage.
•
EMI fi lter.
•
(Protection by fuse (on the bottom of the regulator includes
a spare fuse).
•
Protection against overvoltage.
•
Setting jumpers through the reference voltage (single
phase and three phase voltage range).
•
Setting the excitation type (standard or PMG).
•
Set jumper through the remote control of voltage
•
Using a software called AVRTerm to confi gure the controller,
get alerts and the evolution in time of voltage.
•
The voltage regulation and stability through trimmers.
24
Adjusting the underfrequency
A frequency control progressively deactivates the machine
when the drive motor speed drops below a pre-set,
adjustable threshold preventing over-excitement at low
operating speeds and abating the load engage effects on
the motor.
With jumper J1 inserted, the regulator is set at the threshold
of 47 Hz and when the jumper J1 is removed by using the
solution at 60Hz the threshold for action is set to 57Hz (to
change the regulation of underspeed is necessary to use
Software AVRTerm).
Limit excitation
The limit of excitation is adjustable from 0 to 100% in increments
of 0.1%. When the excitation exceeds its limit, the controller is
in alarm condition (alarm is visible with the software AVRTerm).
The
excitement
is
the
short-circuito.
The
machines will be adjusted at the factory to 100%.
RS485 communication port
The
AVR
has
port
to
communicate
The connection is via a form of conversion RS485/USB, the
USB connection is direct to the PC, the RS485 connection
to the AVR
Communication software
AVRTerm
is
a
communication
(using
Windows
operating
communicate
with
The extreme ease of use allows its immediate use.
Reference voltage
The
voltage
of
the
terminals A, B and C. The sensing may be single-
phase
or
three
The digital controller has a higher precision than the analog
version because it reads the rms voltage (not the average
value).
the
maximum
value
limit
excitation
to
a
RS485
communication
with
the
software
system),
created
the
digital
regulator
generator
is
monitored
phase
(maximum
during
all
the
PC.
for
PC
to
DBL1.
on
500
Vac).