• LED Does Not Turn ON
Check whether the generator output indicator is ON during
engine operation.
Check the remote control box (P. 15-3).
Check the remote control harness for open or short circuit and
for proper connection.
Check the harness connecting the remote control harness and
GCU for open or short circuit and for proper connection.
REMOTE
CONTROL
HARNESS
Viewed from terminal side
Turn the ignition switch OFF and then start the engine and
recheck. Replace the GCU, if the LED does not come on (P. 6-6).
On
Normal
Normal
Wire harness check points
CONTROL WIRE HARNESS
G/Bu
Br/Bu
Normal
Off
Normal voltage
Abnormal
Abnormal
Abnormal
GCU
GCU
Bu: BLUE
Br: BROWN
G: GREEN
Check for AC output voltage at
receptacle.
Low or no voltage
Perform the "No AC Output"
troubleshooting (P. 2-45).
Turn the ignition switch OFF and
then
start
the
engine
and
recheck. Replace the GCU, if the
LED does not come on (P. 6-6).
Repair or replace the remote
control box (P. 15-1 and 2).
Repair or replace the remote
control harness.
Replace or repair the control wire
harness.