3.5.4. Condensate discharge

As the evaporator recovers the heat from the moist extract air, it causes condensation of the water vapour contained in the air.
This water, collected in a tray, is discharged using a 12 mm diameter clear pipe, supplied and fitted to the product.
Connect the discharge pipe to the wastewater ductwork with the accessory supplied (diaphragm adapter to
connect the condensate tube to a 32 mm diameter PVC pipe), taking care to provide for a flow water trap
and fill in with water (a diaphragm water trap can also be used that does not have to be filled with water).
Check the routing of the pipe once connected to avoid it catching anywhere.
Condensate pipe
Safety switch
Mains water
inlet
inlet
Membrane union
Wastewater outlet
(drains)
Water trap
Diagram 1
Identical for T.Flow

3.6. Electrical connection

The thermodynamic water heater must have a constant supply to guarantee the production of DHW and the
operation of the titanium impressed current anode.
The thermodynamic water heater must not be electrically connected until it has been filled with water and the
ducts connected. Never supply the heating element directly with power.
The thermodynamic water heater power supply is single-phase current 230 V-50 Hz + Earth. It must be fitted by a professional
and comply with standard NF C 15-100 or the stipulations in force in the country where the water heater will be installed.
The electrical installation must include:
• A 16 A omnipolar circuit breaker with at least 3 mm opening of contacts,
• 30 mA differential circuit breaker protection.
Permanent power supply
Off-peak power supply*(off-peak/peak)
To create the electrical connection:
• Remove the access hatch from the terminal block using a screwdriver,
• Connect the electric cables to the terminal block according to the pricing structure (see next diagrams),
• Reinsert the cable clamp (and screw in the hatch).
Identical
T.Flow
Nano
®
Condensate pipe
Membrane union
Wastewater outlet
(drains)
Water trap
Diagram 1
Nano
®
Connection terminals Power supply cables
Access hatch
L
L
N 4 5
+
+
Safety switch
Mains water
Water trap
inlet
3G 1.5 mm
L,
, N
4, 5
2G 1.5 mm

Front panel

50
Condensate pipe
Safety switch
Membrane union
Mains water
Water trap
inlet
Wastewater outlet
(drains)
Diagram 2
Diagram 2
Condensate tube: to be connected to the
wastewater flow water trap
Circuit breaker protection
16 A
2
2 A
2
for
L
N 4 5
+
Cable clamp
Condensate pipe
Membrane union
Wastewater outlet
(drains)
+