FINCTION PROGRAMMING (DIP SWITCH SW2)
The settings are stored during the rest phase (door closed).
DIP
STATUS
FUNCTION
ON
PHOTO 1 DISABLED
DIP 1
OFF
PHOTO 1 ENABLED
ON
PHOTO 2 DISABLED
DIP 2
OFF
PHOTO 2 ENABLED
ON
CLOSING LIMIT SWITCH DISABLED
DIP 3
OFF
CLOSING LIMIT SWITCH ENABLED
ON
OPENING LIMIT SWITCH DISABLED
DIP 4
OFF
OPENING LIMIT SWITCH ENABLED
DEFAULT SETTINGS (DIP SWITCH SW2)
DIP 1 ON: PHOTO 1 DISABLED
DIP 2 ON: PHOTO 2 DISABLED
DIP 3 ON: CLOSING LIMIT SWITCH DISABLED
DIP 4 ON: OPENING LIMIT SWITCH DISABLEDSA APERTURA
TRIMMER ADJUSTEMENT
The trimmers TR1, and TR4 can be adjusted also during gate movement and thus the effect immediately
checked. The trimmers TR2, TR3 and TR5 are stored only during the rest phase (gate closed).
Trimmers Function Description
Adjusts the DECELERATION level. Turning the trimmer clockwise the gate speed/force is increased)
TR1
SLOW
NB. With an electromechanical motor (DIP 5 OFF) the trimmer is uninfluential and deceleration will be fixed.
Adjusts the CLOSING TIME from 2 to 100 seconds if JP2 is open. The value is increased by turning the trimmer clockwise.
TR2
CLOSE
Adjusts the CLOSING TIME from 2 to 200 seconds if JP2 is closed. The value is increased by turning the trimmer clockwise.
Adjusts the PAUSE TIME from 2 to 200 seconds. The value is increased by turning the trimmer clockwise.
TR3
PAUSE
Adjusts the motor FORCE level. The force is increased by turning the trimmer clockwise.
TR4
FORCE
NB. IN CASE OF HYDRAULIC OPERATORS THE FORCE MUST BE AT MAXIMUM
Adjusts the OPENING TIME from 2 to 100 seconds if JP1 is open. The value is increased by turning the trimmer clockwise.
OPEN
TR5
Adjusts the OPENING TIME from 2 to 200 seconds if JP1 is closed. The value is increased by turning the trimmer clockwise.
DEFAULT SETTINGS
TRIMMERS TR1, TR2, TR3, TR4, TR5 are adjusted to halfway their travel.