Commissioning
6.1
Basic settings via DIP switch
Changes made via the DIP switches only
take effect after restarting the product.
u Disconnect product from voltage if necessary.
6.1.1 Configuring the product
The tasks described in this section may only
be carried out by a qualified electrician.
In the top section of the housing, there are two 8-
pin DIP switches, with which the device can be con-
figured. In the delivery state, all DIP switches are
switched off ("OFF"). On delivery, the product is
ready for connection.
Fig. 11: DIP switch (delivery state)
1
Bank S1
2
Bank S2
Note the label on the housing.
The following functions can be set via the DIP
switches:
18
8 7 6 5 4 3 2 1
Bank S1
DIP
Function
switch
1
LED display colour scheme
n "OFF":
n "Standby" symbol = blue
n "Charging" symbol = green
n "ON":
n "Standby" symbol = green
n "Charging" symbol = blue
2
Unbalanced load limitation
n "OFF": Unbalanced load limitation off
n "ON": Unbalanced load limitation on
3
Authorisation
n "OFF": No authorisation (Autostart)
n "ON": Authorisation through RFID
4
Using Modbus RTU
n "OFF": Modbus RTU is not used
n "ON": Modbus RTU is used
5
Master / Satellite
n "OFF": Configuration as master
2
n "ON": Configuration as satellite
6
Type of energy meter
n "OFF": Siemens PAC1600 7KT1661
1
n "ON": TQ Energy Manager EM 420 /
KOSTAL Smart Energy Meter
7
Solar charging
n "OFF": Solar charging deactivated
n "ON": Solar charging activated
8
Without function
Bank S2
DIP
Function
switch
1, 2, 3
Max. charging current
4, 5
Reduced charging current when down-
grade input is energised
6,7,8
Max. amperage - building connection