5
1) Specify CODE No. [14] TEMP.
/
buttons.
(CODE No. [14]: Group address)
2) Change the SET DATA from [0001] to [0002]
TIME
/
buttons.
(SET DATA [Header unit: 0001]
[Follower unit: 0002])
3) Push
button.
In this time, the setup finishes when the display
changes from flashing to lighting.
Indoor UNIT No. before setup change is displayed.
6
If there is other indoor unit to be changed,
2
5
repeat procedure
to
to change the setup.
When the above setup has finished, push
to select the indoor UNIT No. before change of
setup, specify CODE No. [12], [13], [14] in order
with TEMP.
/
buttons, and then check the
changed contents.
Address change check Before change:
[3-3-1] → After change: [2-2-2]
Pushing
button clears the contents of which
setup was changed.
2
(In this case, procedure from
is repeated.)
Indoor UNIT No. before setup change is displayed.
41-EN
7
After check of the changed contents,
push
button.
(Setup is determined.)
When
button is pushed, the display disappears
and the status becomes the usual stop status.
(When
button is pushed the operation from
the remote controller is not accepted for approx.
1 minute.)
*If the operation from the remote controller is
not accepted even 1 minute or more passed
after pushing
button, it is considered that the
address setup is incorrect.
In this case, the automatic address must be again
set up.
Therefore repeat procedure of the setup change
1
from the Procedure
.
To recognize the position of the
corresponding indoor unit though the indoor
UNIT No. is known
Check the position during operation stop.
(Stop operation of the set.)
1
1,3
2
– 21 –
1
Push
+
buttons simultaneously for 4
seconds or more.
After a while, the display part flashes and the
display appears as shown below.
In this time, the position can be checked because
fan of the indoor unit operate.
• For the group control, the indoor UNIT No. is
displayed as [
] and fans of all the indoor
units in the group control operate.
Check the displayed CODE No. is [01].
• When the CODE No. is other than [01], push
button to erase the display and repeat procedure
from the first step.
(After pushing
button, operation of the
remote controller is not accepted for approx. 1
minute.)
(* Display changes according to
the model No. of indoor unit.)
2
In the group control, every time
is pushed, the indoor UNIT No. in the group
control is displayed in order.
In this time, the position of the indoor unit can be
confirmed because only fan of the selected indoor
unit operate.
(For a group control, No. of the firstly displayed
indoor unit becomes the header unit.)
3
After confirmation, push
button to return
the mode to the usual mode.
When
button is pushed, the display disappears
and the status becomes the usual stop status.
(When
button is pushed the operation from
the remote controller is not accepted for approx.
1 minute.)
■
8°C operation
Pre-heating operation can be set for cold regions
where room temperature drops to below zero.
1
Push
+
+
buttons simultaneously for
4 seconds or more when the air conditioner is
not working.
After a while, the display part flashes as shown
below. Check the Displayed CODE No. is [10].
• When the CODE No. is other than [10], push
button to erase the display and repeat procedure
from the first step.
(After pushing
button, operation of the
remote controller is not accepted for approx. 1
minute.)
(* Display changes according to
the model No. of indoor unit.)
2
Every time
button is pushed, the indoor
button
unit No. in the group control is displayed in
order.
Select the indoor unit of which setup is changed.
In this time, the position of the indoor unit of which
setup is changed can be confirmed because fan of
the selected indoor unit operate.
3
Specify CODE No. [d1] TEMP.
/
buttons.
4
Select SET DATA [0001] TIME
/
buttons.
SET DATA
8°C Operation setting
None
0000
(Factory default)
0001
8°C Operation setting
5
Push
button.
In this time, the setup finishes when the display
changes from flashing to lighting.
6
Push
button. (Setup is determined.)
When
button is pushed, the display disappears
and the status becomes the usual stop status.
(When
button is pushed the operation from
the remote controller is not accepted for approx.
1 minute.)
42-EN