Descargar Imprimir esta página

Toshiba RAV-GM901CTP-E Manual De Instalación página 26

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 114
Wired
Wireless remote
remote
controller Sensor
controller
block display of
display
receiving unit
Main defective parts
Operation
Timer
Indication
Flashing
Ready GR
GR OR
F31
SIM Outdoor unit P.C. board
Outdoor unit compressor
H01
breakdown
H02
Outdoor unit compressor lock
Outdoor unit current detect
H03
circuit error
H04
Case thermostat operation (1)
Outdoor unit low- pressure
H06
system error
Duplicated header indoor
L03
SIM
units
Group line in individual indoor
L07
SIM
unit
L08
SIM Indoor group address not set
L09
SIM Indoor unit capacity not set
L10
SIM Outdoor unit P.C. board
L20
SIM LAN communication error
L29
SIM Other outdoor unit error
Abnormal external input into
L30
SIM
indoor unit (interlock)
L31
SIM Phase sequence error, etc.
Outdoor unit discharge temp.
P03
ALT
error
Outdoor unit high- pressure
P04
ALT
system error
P05
ALT Open phase detected
P07
ALT Heat sink overheat
Indoor unit water overflow
P10
ALT
detected
P12
ALT The fan error of the indoor unit
P15
ALT Gas leakage detected
49-EN
Judging
Parts to be checked / error description
device
Outdoor P.C. board --- In the case of EEPROM
Outdoor
error.
Current detect circuit, power voltage --- Minimum
frequency was reached in the current releasing
Outdoor
control or short-circuit current (Idc) after direct
excitation was detected
Compressor circuit --- Compressor lock was
Outdoor
detected.
Current detect circuit, outdoor unit P.C. board
Outdoor
--- Abnormal current was detected in AC-CT or a
phase loss was detected.
Outdoor
Malfunction of the case thermostat
Current, high-pressure switch circuit, outdoor
P.C. board --- Ps pressure sensor error was
Outdoor
detected or low-pressure protective operation was
activated.
Indoor address setting error --- There are two or
Indoor
more header units in the group.
Indoor address setting error --- There is at least
Indoor
one group-connected indoor unit among individual
indoor units.
Indoor address setting error --- Indoor address
Indoor
group has not been set.
Indoor
Indoor unit capacity has not been set.
In the case of outdoor P.C. board jumper wire
Outdoor
(for service) setting error
Network
Address setting, central control remote controller,
adapter
network adapter --- Duplication of address in
central
central control communication
control
Other outdoor unit error
1) Communication error between IPDU MCU and
Outdoor
CDB MCU
2) Abnormal temperature was detected by the
heat sink temp. sensor in IGBT.
External devices, outdoor unit P.C. board
Indoor
--- Abnormal stop due to incorrect external input
into CN80
Power supply phase sequence, outdoor unit
Outdoor
P.C. board --- Abnormal phase sequence of the
3-phase power supply
An error was detected in the discharge temp.
Outdoor
releasing control.
High-pressure switch --- The IOL was activated
Outdoor
or an error was detected in the high-pressure
releasing control using the TE.
The power wire may be connected incorrectly.
Outdoor
Check open phase and voltages of the power
supply.
Abnormal temperature was detected by the temp.
Outdoor
sensor of the IGBT heat sink.
Drain pipe, clogging of drainage, float switch
Indoor
circuit, indoor P.C. board --- Drainage is out of
order or the float switch was activated.
Indoor fan motor, indoor P.C. board --- Abnormal
Indoor
operation (over current or lock, etc.) is detected.
There may be gas leakage from the pipe or
Outdoor
connecting part. Check for gas leakage.
– 25 –
Wired
Wireless remote
remote
controller Sensor
controller
block display of
Air
display
receiving unit
conditioner
Operation
status
Timer
Indication
Flashing
Ready GR
GR OR
Entire
stop
P19
ALT 4-way valve error
Entire
High-pressure protective
P20
ALT
stop
operation
Entire
P22
ALT Outdoor unit fan error
stop
Entire
Outdoor unit inverter Idc
stop
P26
ALT
activated
Entire
stop
P29
ALT Outdoor unit position error
Entire
stop
P31
ALT Other indoor unit error
Entire
: Lighting,
: Flashing,
stop
The air conditioner automatically enters the auto-address setting mode.
Entire
ALT: When two LEDs are flashing, they flash alternately.
stop
SIM: When two LEDs are flashing, they flash in synchronization.
Entire
Receiving unit display OR: Orange GR: Green
stop
Entire
stop
Entire
stop
Auto-
reset
Entire
stop
Entire
stop
Entire
stop
Operation
continued
(thermost at OFF)
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Judging
Main defective parts
Parts to be checked / error description
device
4-way valve, indoor temp. sensors (TC/TCJ) --- An
Outdoor
error was detected due to temperature drop of the
(Indoor)
indoor unit heat exchanger sensor when heating.
Outdoor
High-pressure protection
Outdoor unit fan motor, outdoor unit P.C. board ---
Outdoor
An error (overcurrent, locking, etc.) was detected
in the outdoor unit fan drive circuit.
IGBT, outdoor unit P.C. board, inverter wiring,
compressor --- Short-circuit protection for
Outdoor
compressor drive circuit devices (G-Tr/IGBT) was
activated.
Outdoor unit P.C. board, high-pressure switch ---
Outdoor
Compressor motor position error was detected.
Another indoor unit in the group is raising an
Indoor
alarm. E03/L07/L03/L08 alarm check locations
and error description
: Goes off
Air
conditioner
status
Auto-
reset
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Auto-
reset
50-EN

Publicidad

loading