5
Installation
5.1
5.1.1
SmartConnect
Operating manual
Installation instructions
If no fuses are integrated in the central inverter or if these are greater
|
than 240 A:
Each SmartConnect must be fuse-protected to a maximum of 240
|
A.
The auxiliary power supply must be fuse-protected with a maximum of
|
16 A.
Configure and fuse the electric circuit of the auxiliary power supply
|
according to the system-specific residual current concept.
Max. 240 A
(3)
(4)
5.1:
Wiring of the DC main cables
(1) SmartConnect
(2) Additional SmartConnect (optional)
(3) Fuse protection max. 240 A
(4) Central inverter
(1)
L N PE
(4)
PE
N
L
(3)
Max. 16 A
5.2:
Wiring diagram for the auxiliary power supply
(1) SmartConnect
(2) Additional SmartConnect (optional)
(3) Fuse protection max. 16 A, characteristic B
(4) Auxiliary power supply
Prerequisites
Before performing any work on the device, note the following safety rules:
5 Installation
(1)
L NPE
L NPE
L N PE
(2)
(2)
27