Specifications
SmartConnect
Operating manual
SmartConnect
DC input data (direct current)
Input string terminal
String connections
Measuring channels
String current per input series
terminal
String voltage
Terminal diameter for cable lead-
through
DC output data
DC main connection terminals,
cable section
Main cable connections
Output current
Power rating of the main
connection terminals
Terminal diameter for cable lead-
through
Disconnection function
Manual
Automatic
Type of disconnection
Communications
Communications
General data
Ambient temperature
Protection type / protection class
Auxiliary power supply
Failure bypass
Specifications
2
1.5–6 mm
8, maximum 10 module strings in
parallel per string connection.
8
Max. 20 A
Max. 1000 V
5–10 mm
2
50–150 mm
fixed or flexible.
2
Max. 160 A
Max. 240 A
14–21 mm
Local and remote operation.
RealProtect
Protection range:
Forward current > 20 A
Reverse current < –1 A
Undervoltage < 300 V
Surge voltage > 1000 V
Mutual galvanic isolation
CANopen via CAN distributor.
–20 °C to +50 °C
IP55 / I
230 V ( 20 %) / 50–60 Hz / 20 VA,
in switch-on torque of relay
80 VA for max. 5 seconds.
Max.150 ms
71