Descargar Imprimir esta página

Roger Technology B70/1T Instrucciones Y Advertencias Para El Instalador página 61

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 147
8.3
TEST mode
To activate the mode, press the TEST button with the automatic door system at rest. If the gate is moving, pressing
TEST stops the gate. Pressing the button again enables TEST mode.
device is activated.
No safety device in alarm state and no limit switch activated.
(Sb)
Release pin rotated.
STOP contact (N.C.) open.
If there is no STOP switch, jumper the contact.
Sensing edge contact COS1 (N.C.) is open. Check connection.
If sensing edge is not installed, disable with
Sensing edge contact COS2 (N.C.) is open. Check connection.
If sensing edge is not installed, disable with
Photocell contact FT1 (N.C.) is open. Check connection.
If photocell is not installed, disable with
Photocell contact FT2 (N.C.) is open. Check connection.
If photocell is not installed, disable with
Both limit switches in error state.
Check connections and settings of limit switches.
If gate is open, gate open limit switch is detected.
If gate is closed, gate closed limit switch is detected.
NOTA: If one or more contacts are open, the gate will not open or close. This does not apply for the limit switch signal
state, however, which is shown on the display but does not prevent normal operation of the gate.
the next device is displayed. Any further alarm states are also displayed with the same logic.
Press the TEST button again to exit test mode.
After 10 seconds with no user input, the display returns to command and safety device state display mode.
8.4
Standby mode
POWER
The command signal status is shown on the left hand side of the display for
5 seconds, ONLY when the respective command signal is active (AP, CH, PP,
PE, OR). For example, if the gate open command is activated, the letters AP
appear on the display.
the display. The number of the terminal relative to the safety device in alarm
When the gate is completely open or completely closed,
on the display to indicate that the gate has reached the gate open limit
switch
or gate closed limit switch
Example: STOP contact in alarm state
.
.
This mode is activated after 30 minutes with no user input. The POWER LED
Press UP
, DOWN
, + , - to reactivate the control unit.
NOTE: If a safety password (only if active) is unlocked, to adjust the parameter
settings, the password is automatically reactivated in Stand By mode.
.
.
.
or
is shown
61

Publicidad

loading