Descargar Imprimir esta página

Roger Technology B70/1T Instrucciones Y Advertencias Para El Instalador página 68

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 147
Enabling operator present function
Disabled.
Enabled. The open (AP) or close (CH) button must be pressed continuously to operate the gate. The gate stops when
the button is released.
Gate open indicator / photocell test function and "battery saving"
The indicator is off when the gate is closed, and steadily lit during manoeuvres and when the gate is open.
quickly during closing manoeuvres.
If the gate is stopped in an intermediate position, the lamp extinguishes twice every 15 seconds.
Set
Set to
When the gate is completely open or closed, the controller unit deactivates any accessories connected to terminal SC
to reduce battery consumption.
Set to
Setting deceleration during opening and closing
See chapters 13 and 14
Setting gate open limit switch constant speed approach distance
N.B.: the manoeuvre speed is set with parameter
switch at constant speed.
Setting gate closed limit switch constant speed approach distance
N.B.: the manoeuvre speed is set with parameter
switch at constant speed.
= Approximate 15 cm distance; ...
Partial opening adjustment (%)
N.B.: This parameter is set to 50% (half of total gate travel) by default.
From 10% to 99% of total gate travel.
Adjusting automatic closing time after partial opening
Pause time settable from 00 to 90 s.
Pause time settable from 2 to 9 min.
Type of signaling provided by COR output
STANDARD operation managed by parameter
Contact closed if the control unit is working properly.
Contact open if central locked in alarm.
Contact closed if the control unit is powered by the mains or charged battery.
Open contact due to a fault: control unit powered by low battery (voltage level set by par.
(the control unit no longer accept commands).
Closed contact if none of the fault related situations 1 and 2 occurs.
Open contact if at least one of the fault related situations 1 and 2 occurs.
Closed contact if the gate is not completely open.
Open contact if the gate is completely open.
Closed contact if the gate is not completely closed.
Open contact if the gate is completely closed.
Setting automatic closing time
The timer starts from the gate open state and continues for the set time. Once the set time is reached, the gate closes
automatically. The timer count restarts if a photocell is triggered.
Pause time settable from 00 to 90 s.
Pause time settable from 2 to 9 min.
68
= the gate decelerates long before the mechanical
. After decelerating, the gate completes the distance to the limit
. After decelerating, the gate completes the distance to the limit
= Approximate 30 cm distance; ...
= Approximate 120 cm distance.
.
) or with error alert

Publicidad

loading