Safety input and command status (TEST mode)
With no currently active commands, press the TEST button and check the following:
DISPLAY
POSSIBLE CAUSE
The release handle is open.
(00 Sb)
The safety STOP contact is open.
Sensing edge COS1 not connected
or incorrectly connected.
Sensing edge COS2 not connected
or incorrectly connected.
Photocell FT1 not connected or in-
correctly connected.
Photocell FT2 not connected or in-
correctly connected.
Both limit switches in open contact
state or not connected.
Gate is at gate closed limit switch.
Gate open limit switch absent or not
connected.
Gate is at gate closed limit switch.
Gate closed limit switch absent or
not connected.
If occurs with no voluntary com-
mand, the contact (N.O.) may be
faulty or one of the buttons may be
incorrectly connected.
If occurs with no voluntary com-
mand, the contact (N.O.) may be
faulty or the timer may be incorrect-
ly connected.
N.B: press TEST to exit TEST mode.
We recommend troubleshooting safety device and input status errors with "corrective action by software" only.
78
ACTION BY SOFTWARE
-
-
Set the parameter
if not used
or to disable
Set the parameter
if not used
or to disable
Set the parameter
e
not used or to disable
Set the parameter
e
not used or to disable
-
If the limit switch state indicated is
incorrect, check the setting of para-
meter
.
-
If the limit switch state indicated is
incorrect, check the setting of para-
meter
.
-
-
-
-
-
-
PHYSICAL CORRECTIVE ACTION
Close the release handle and turn the key
to the close position.
Check that the release contact is con-
nected correctly.
Install a STOP button (NC) or jumper the
ST contact with the COM contact.
Jumper contact COS1 with contact COM,
if not used or to disable
Jumper contact COS2 with contact COM,
if not used or to disable
if
Jumper contact FT1 with contact COM, if
not used or to disable. Check connection
referring to relative connection diagram.
if
Jumper contact FT2 with contact COM, if
not used or to disable. Check connection
referring to relative connection diagram.
Check connection of limit switches.
In the absence of limit switches, check
that par.
is set to
.
-
Check connection of limit switches.
In the absence of limit switches, check
that par.
is set to
.
-
Check connection of limit switches.
In the absence of limit switches, check
that par.
is set to
.
Check PP - COM contacts and con-
nections to buttons.
Check CH - COM contacts and con-
nections to buttons.
Check AP - COM contacts and con-
nections to buttons.
Check PED - COM contacts and con-
nections to buttons.
Check ORO - COM contacts. Contact
must not be jumpered if not used.