Connect and open the coupling to the A/C system, then press
the following screen will be displayed:
During the recovery phase, the machine displays the quantity of refrigerant recovered, in
grams. Upon completion of recovery, the machine will stop and discharge, while automatically
displaying the used oil extracted from the A/C system during the recovery phase. The oil
discharge operation lasts 4 minutes.
The machine checks whether or not there is air in the bottle and, if necessary, purges the non-
condensable gas; The machine will automatically discharge any non-condensable gas.
Allowing the machine to fully complete the procedure will reduce the risk of return flows, which
may cause excessive non-condensable gas to be recharged into the air conditioning system. If
any residual refrigerant in the A/C system should increase in pressure during this phase, the
machine will automatically begin recovering the refrigerant. Following screen will be displayed:
INSTRUCTIONS MANUAL
MANUAL / RECOVERY
Please wait ...
Refrigerant recovered
A/C pressure
0 g
Oil recovered
6.31 bar
0 ml
AUTOMATIC / RECOVERY
Refrigerant recovery
Refrigerant recovered
A/C pressure
120 g
Oil recovered
2 bar
0 ml
MANUAL / RECOVERY
Oil recovery
Refrigerant recovered
A/C pressure
500 g
Oil recovered
0 bar
10 ml
MANUAL / RECOVERY
Close and disconnect HP and LP couplings
from A/C system
Refrigerant recovered
500 g
-40-
, press
DD/MM/YY XX:XX PM
Tank pressure
6.71 bar
Tank temperature
22.0°C
DD/MM/YY XX:XX PM
Tank pressure
6.71 bar
Tank temperature
22.0°C
DD/MM/YY XX:XX PM
Tank pressure
6.81 bar
Tank temperature
22.0°C
DD/MM/YY XX:XX PM
Oil recovered
10 ml
to return back.