Connect and open the coupling (HP, LP, or HP/LP, depend of the previous choice) connected
to the A/C system, then press
The machine will start the filling with the preset quantity of refrigerant.
Then the following screen will be displayed:
Unscrew HP and LP coupling without disconnect from A/C system end press
The machine will recover the residual refrigerant into the service hoses, then the following
screen will be displayed:
Disconnect coupling from A/C system.
Procedure is now successfully completed.
NOTE: Rarely, charging may not run to completion due to pressure balance. In this case, close
the high pressure tap (leaving the low-pressure side open), and switch on the A/C system.
Press the symbol
INSTRUCTIONS MANUAL
, press
MANUAL / CHARGE
Charge
Refrigerant charged
200 / (100%)
Tank pressure
7 bar
0 ml / 0 ml
MANUAL / OIL-UV INJECTION
Close HP and LP couplings without disconnected
from A/C system and press to continue
MANUAL / CHARGE
Empty hoses
Hoses pressure
4.01 bar
MANUAL / CHARGE
END OF PROCEDURE
Disconnected HP and LP coupling from A/C system
Refrigerant charged
200 g
for printing.
to return back.
DD/MM/YY XX:XX PM
A/C pressure
4.85 bar
Tank temperature
22 °C
DD/MM/YY XX:XX PM
DD/MM/YY XX:XX PM
DD/MM/YY XX:XX PM
-49-
to continue: