Press
to continue, or press
Connect and open the coupling connected to the A/C system, then press
vacuum phase
When time of check is reached, the machine will test for leaks in the A/C system:
(WARNING! If vacuum time is lower than 15 minutes this test is not reliable). If leaks are
found, the machine will stop automatically and display the A/C SYSTEM LEAKS alarm.
Detection of micro-leaks is not guaranteed.
At the end of the preset vacuum time, the machine will sound and alarm and the following
screen will be displayed:
Close and disconnect HP and LP coupling from A/C system, then press
MAIN MENU; VACUUM PROCEDURE is now successfully completed.
INSTRUCTIONS MANUAL
to go back.
MANUAL / VACUUM
Connect and open HP and LP couplings
To A/C system and press to continue
MANUAL / VACUUM
Vacuum
01:57
A/C pressure
0 bar
MANUAL / VACUUM
DD/MM/YY XX:XX PM
Leak test
00:51
A/C pressure
-0.99 bar
MANUAL / VACUUM
Close and disconnect HP and LP couplings
from A/C system
Vacuum time
15 min
-42-
DD/MM/YY XX:XX PM
DD/MM/YY XX:XX PM
DD/MM/YY XX:XX PM
Time of check
10 min