5 Installation
5.7.4
Mounting the indoor unit
Fig.190
4
5
Clic !
5.7.5
Installing the condensate pipe
Fig.191
2
5.8
Positioning the cassette unit
5.8.1
Installation location
Fig.192
1500
1500
1500
174
It is possible to install the indoor unit using the existing side pre-shearing
or lead the pipes behind the unit. The wiring, the drain, and the refrigerant
connections are fully suited for connection on either side of the unit.
1. Choose if the pipes need to pass behind or next to the indoor unit.
2. Drill a 70 mm diameter hole in the wall with a downward gradient from
the indoor unit to the outdoor unit.
3. Fit the indoor unit ring to the wall with adhesive tape.
4. Hang the indoor unit on the mounting bracket using the upper hooks.
Make sure that the indoor unit is centered.
5. Position and push the indoor unit onto the mounting bracket until the
hooks attach firmly into the guides and you hear them click into place.
It is possible to install the condensate pipe on the right side (1) or the left
side (2) of the indoor unit.
1. If needed, remove the rubber cap from the chosen condensation
connector and plug it onto the unused connector.
2. Fit the condensate pipe to the condensation connector.
3. Install the condensate pipe with a downward slope of 1/100-150.
MW-6020077-01
1
Select a suitable position in order to achieve a uniform air temperature
in the place of installation.
Adhere to the minimum distances between other objects and obstacles.
Make sure that there is space to install the condensate pipe with a slope
on the chosen location.
1500
MW-6070069-01
Caution
Ensure that the installation location is able to take four times the
unit weight and capable of bearing vibration for long periods.
7800852 - v02 - 10052022