5 Installation
5.10.3
Installing the condensate pipe
Fig.205
1~1.5 m
5.11
Connecting the wired controller to the ducted unit
Fig.206
12v GND A
B
180
2. Install a nut to the end and a spring washer to the suspension bolt.
3. Install the indoor unit to the suspension bolt, and use a washer and a
nut to secure.
4. Adjust the relative position of the suspension hook on the suspension
bolt so that the unit can be in level position in all directions.
5. Tighten the bolt and ensure that four hooks are in close contact with
the nuts and washers, to fix the indoor unit under the ceiling.
6. Ensure the unit is secure and does not shake or sway.
7. Connect the wired controller to the ducted unit.
8. Connect the air inlets and outlets to the duct according to the
MW6020097-01
construction plan.
9. Close off any unused drain taps on the unit.
1. Connect the condensate pipe to the drain tap.
2. Ensure there is a downward gradient of 1/100-150. The pipe should
not rise at any point.
3. Insulate the condensate pipe and drain tap to prevent condensation.
4. Start the air conditioner.
5. Pour water directly into the condensate pan.
>1/100
6. Check that the water is drained off smoothly and correctly.
MW-6020089-1
1. Connect the wired controller to the terminal of the indoor unit
connector as shown on the figure. Use the cables provided with the
wired control.
2. Test the wired controller during commissioning.
MW6020164-02