Baxi LSGT40-2M Manual De Instalación Y Mantenimiento página 175

Aire acondicionado multi-split

Publicidad

Idiomas disponibles

Idiomas disponibles

Fig.193
1500
1 Indoor unit
2 Lighting
5.8.2
Suspending the unit
5.8.3
Installing the condensate pipe
7800852 - v02 - 10052022
50
1
1500
2500
2000
1. Mount the fasteners of the indoor unit in one of the following ways:
MW6020094-01
2. Install a nut to the end and a spring washer to the suspension bolt.
3. Install the indoor unit to the suspension bolt then a washer and a nut
4. Adjust the relative position of the suspension hook on the suspension
5. Tighten the nut and ensure that four hooks are in close contact with
6. Install the locknut and screw it down to secure the installation.
7. Ensure the unit is secure and does not shake or sway. Ensure that the
MW6020097-01
1. Connect the condensate pipe to the drain tap.
2
3
4000
3 Fan
Important
Ensure that the installation location is able to take four times the
unit weight and capable of bearing vibration for long periods.
Ensure the condensate can properly be drained. Install the unit
slightly sloped towards the drain tap.
with a dowel on which the suspension bolt is screwed.
with a suspension rod fixed directly on the hard structure (steel or
wood).
to secure.
bolt so that the unit can be in level position in all directions.
the nuts and washers, to fix the indoor unit.
center of the indoor unit is aligned with the installation.
The unit includes a condensate pump with a 700 mm lift up
capacity. However after the pump stops, the water still in the pipe
will condensate back and may overflow the drain pan causing a
water leak. To prevent this, ensure there is a downward gradient
of 1/100-150 after the highest point in the pipe.
en
5 Installation
1
MW-6070070-01
175