Maximum refrigerant pipe
length
5.12.10 Add refrigerant if necessary
5
7800852 - v02 - 10052022
Unit
LSGT40-2M
LSGT50-2M
g/m
25
25
m
40
40
Check the length of the refrigerant connection pipes. Depending on their
length, add the required quantity of refrigerant.
2
1. Turn off the air conditioner.
4
2. Close the gas line.
3. Remove the protection cap from the refill valve.
4. Install the refill bottle with pressure gauge and open the gas line.
5. Start the refilling process.
6. Stop refilling at the desired and necessary pressure and close the gas
7. Screw the protection cap back on the refill valve.
MW-6020078-01
8. Open the gas line.
9. Check that there are no leaks on the circuit or the refill valve.
LSGT60-3M
LSGT70-3M
25
25
60
60
Important
Respect the maximum refrigerant charge for the system.
See also
Refrigerant pipe length, page 167
line.